ELE15-04103
| Conference | 1/7/2016 | 1/11/2016 | 1/11/2016 1:49:45 PM | P | DONE |
|
|
This consultation will be for upgrading the existing gear. Please give me a call beforehand so I can meet you there. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins discussed replacing old guts in panel board and installing new panel inside. Contractor will fabricate deed front to protect conductors and personnel
|
ELE15-03670
| Final | 1/11/2016 | 1/11/2016 | 1/11/2016 1:43:17 PM | P | FAIL |
|
|
Lock box is in mailbox and the code is 7448 Phone #: ###-#### Inspection requested via web by Randy Fletcher 210.52 (g)(1) branch circuit shall not supply any outlets outside of building 210.8(a)(5) in unfinished basements all 120v receptacles shall have GFCI protection Funds required to permit for final
|
ELE13-01733
| ELE-Aging Inspection | 1/11/2016 | 1/11/2016 | 1/11/2016 12:56:54 PM | | DONE |
|
|
called and left a message
|
ELE15-04101
| Temporary Service | 1/11/2016 | 1/11/2016 | 1/11/2016 12:50:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE16-00075
| Electrical Rough-In | 1/11/2016 | 1/11/2016 | 1/11/2016 12:05:45 PM | P | PASS |
|
|
Please inspect grounding electrode on garage wall. Any questions please call if you have any questions please call ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman grounding electrode on garage wall ok pour
|
ELE15-04128
| Rough-In Permanent Service | 1/9/2016 | 1/11/2016 | 1/11/2016 9:41:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga rough-in ok cover p/s o/h n ok
|
ELE15-04127
| Rough-In Permanent Service | 1/9/2016 | 1/11/2016 | 1/11/2016 9:37:55 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga 334.30 type nm cable shall be within 4 1/2' between supports
|
ELE15-04129
| Electrical Rough-In | 1/9/2016 | 1/11/2016 | 1/11/2016 9:36:46 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga 334.15 type nm cable shall be protected from physical damage
|
ELE16-00049
| Temporary Service | 1/11/2016 | 1/11/2016 | 1/11/2016 9:07:01 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman t/s u/g n ok
|