ELE12-02998
| ELE-Aging Inspection | 1/11/2017 | 1/11/2017 | 1/19/2017 1:22:26 PM | | PASS |
|
|
Will check after snow melt for access. Drove by.
|
ELE12-01429
| ELE-Aging Inspection | 1/11/2017 | 1/11/2017 | 1/19/2017 1:10:43 PM | | DONE |
|
|
Drove by will check when snow has melted off
|
ELE17-00037
| Conference | 1/9/2017 | 1/11/2017 | 1/12/2017 11:07:16 AM | A | DONE |
|
|
Consult about new code requirements in old building. Contact Tom Betty. Phone #: ###-#### Inspection requested via web by Cathy Duchek Discussed electrical requirements of remodel. Walls will not have drywall removed will be repainted. Patches will be created to add microwave circuits. Surface mounted conduits shall be listed assembly, receptacles shall be tamper resistant type, range receptacles shall be 4 wire, bedroom areas not required to be AFCI protected due to no new wiring being installed, check with Building inspector on ADA requirements for units that may be marketed as ADA. Panels may need lowered to comply. Temp wiring feeding sign not compliant, GFCI protection, installed by unlicensed person, shall repair with in 5 working days. Will schedule reinspect for temp wiring for Wed. 1-18-17.
|
ELE16-04041
| Electrical Rough-In | 1/11/2017 | 1/11/2017 | 1/11/2017 1:18:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Checked listing on a LED mud in luminaire with drivers above grid. Discussed GFCI devices located in readily accessible locations. Some noticed above 6'7" on walls and in ceiling. Bar recessed hardlids rough in ok cover
|