FIR16-00163
| INSP-Conference | 1/11/2017 | 1/11/2017 | 1/11/2017 2:25:06 PM | P | DONE |
|
|
Fire conference complete, discussion about location of fire panel annunciator and whether another annunciator would be needed because of knox box location. Current location of annunciator on city approved drawings is acceptable, no others are needed.
|
BLD16-00147
| FIRE-Supply Line Cover | 1/11/2017 | 1/11/2017 | 1/11/2017 1:42:47 PM | P | CANC |
|
|
A voicemail was left on the point of contacts cell phone, Mike at ###-####, this inspection request is cancelled, fire alarms for levels 4 and 5 plus rooms on level 3 have not been tested/inspected, this needs to be completed before life sfatey inspection can be performed for TCO of levels 1-4. Need to verify if fire sprinkler inspections have been completed for levels 1 through 5 for TCO before life safety inspection as well.
|
FIR16-00510
| INSP-Sprinkler Rough-in/Hydro | 1/10/2017 | 1/11/2017 | 1/11/2017 1:10:29 PM | P | PASS |
|
|
Hydrostatic test complete for standpip. Hydrostatic test complete for overhead fire sprinkler piping on levels 1 and 2.
|
NAF16-00053
| INSP-Final | 1/11/2017 | 1/11/2017 | 1/11/2017 12:50:53 PM | P | FAIL |
|
|
Door hardware on exterior door located in area of work (West side warehouse area) needs to be replaced per notes 5 and 6 of the fire code review comments, door currently has round type door hardware and thumbturn deadbolt. Slide bolt on same door needs to be removed per note 5 on fire code review comments.
|
BLD15-01110
| FIRE-Final Inspection | 1/11/2017 | 1/11/2017 | 1/11/2017 12:21:01 PM | P | PART |
|
|
Partial final inspection complete for life fire safety, (TCO authorized on life fire safety per conversation with Scott Arellano) fire sprinkler inspection complete, partial completion for fire alarm system (contractor is troubleshooting sync issue on level 4, fire alarm permit will remain in issued status until issue is resolved), knox box is in place, fire extinguishers are in place with current inspection tags. Fire life safety can be finaled when FIR permit for fire alarms is complete.
|
FIR16-00437
| INSP-Final Inspection | 1/11/2017 | 1/11/2017 | 1/11/2017 12:16:27 PM | P | PART |
|
|
Partial final inspection complete, contractor is troubleshooting the intermittent sync issue on level 4, permit will remain in issued status until issue is resolved.
|
FIR16-00322
| INSP-Final Inspection | 1/11/2017 | 1/11/2017 | 1/11/2017 12:13:36 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR16-00494
| INSP-Sprinkler Rough-in | 1/11/2017 | 1/11/2017 | 1/11/2017 9:40:58 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant fire sprinkler heads located in the ceiling grid area's complete, overhead fire sprinkler piping in ceiling grid area's approved for cover.
|
FIR16-00393
| INSP-Final Inspection | 1/10/2017 | 1/11/2017 | 1/11/2017 9:36:27 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|