Inspections for the day of: Wednesday, January 11, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00163 INSP-Conference1/11/20171/11/20171/11/2017 2:25:06 PMPDONE
Fire conference complete, discussion about location of fire panel annunciator and whether another annunciator would be needed because of knox box location. Current location of annunciator on city approved drawings is acceptable, no others are needed.
BLD16-00147 FIRE-Supply Line Cover1/11/20171/11/20171/11/2017 1:42:47 PMPCANC
A voicemail was left on the point of contacts cell phone, Mike at ###-####, this inspection request is cancelled, fire alarms for levels 4 and 5 plus rooms on level 3 have not been tested/inspected, this needs to be completed before life sfatey inspection can be performed for TCO of levels 1-4. Need to verify if fire sprinkler inspections have been completed for levels 1 through 5 for TCO before life safety inspection as well.
FIR16-00510 INSP-Sprinkler Rough-in/Hydro1/10/20171/11/20171/11/2017 1:10:29 PMPPASS
Hydrostatic test complete for standpip. Hydrostatic test complete for overhead fire sprinkler piping on levels 1 and 2.
NAF16-00053 INSP-Final1/11/20171/11/20171/11/2017 12:50:53 PMPFAIL
Door hardware on exterior door located in area of work (West side warehouse area) needs to be replaced per notes 5 and 6 of the fire code review comments, door currently has round type door hardware and thumbturn deadbolt. Slide bolt on same door needs to be removed per note 5 on fire code review comments.
BLD15-01110 FIRE-Final Inspection1/11/20171/11/20171/11/2017 12:21:01 PMPPART
Partial final inspection complete for life fire safety, (TCO authorized on life fire safety per conversation with Scott Arellano) fire sprinkler inspection complete, partial completion for fire alarm system (contractor is troubleshooting sync issue on level 4, fire alarm permit will remain in issued status until issue is resolved), knox box is in place, fire extinguishers are in place with current inspection tags. Fire life safety can be finaled when FIR permit for fire alarms is complete.
FIR16-00437 INSP-Final Inspection1/11/20171/11/20171/11/2017 12:16:27 PMPPART
Partial final inspection complete, contractor is troubleshooting the intermittent sync issue on level 4, permit will remain in issued status until issue is resolved.
FIR16-00322 INSP-Final Inspection1/11/20171/11/20171/11/2017 12:13:36 PMPPASS
Final fire sprinkler inspection passed/complete.
FIR16-00494 INSP-Sprinkler Rough-in1/11/20171/11/20171/11/2017 9:40:58 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping/pendant fire sprinkler heads located in the ceiling grid area's complete, overhead fire sprinkler piping in ceiling grid area's approved for cover.
FIR16-00393 INSP-Final Inspection1/10/20171/11/20171/11/2017 9:36:27 AMAPASS
Final fire alarm inspection passed/complete