FIR03-00598
| FIR-Aging Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | | PASS |
|
|
project is still in progress 1/12/2004 7:08:42 AM
|
FIR04-00008
| INSP-Sprinkler Rough-in/Hydro | 1/9/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/9/2004 at 11:51:23 AM. Contact: ###-####.
|
FIR03-00800
| INSP-Final Inspection | 1/9/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | A | NR |
|
|
Rick,
We need to request a 2:00 o'clock inspection at 8th floor C.W. Moore T.I.
Call me on my cell phone if you have any problems. ###-####
Thanks
Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
|
BLD02-02126
| FIRE-Final Inspection | 1/9/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | FAIL |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need stairwell signage; verify labels on all rated doors; remove baggies from heads on second floor; clean sprinkler head in HC parking stall; add signage on all sprinler drains; add concealer escutcheons on second floor restroom heads 1/12/2004 3:29:43 PM
|
BLD03-01088
| FIRE-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | FAIL |
|
|
###-#### jim need labels on all rated doors; complete fire alarm permit; complete shell and core 1/12/2004 3:24:57 PM
|
BLD03-01961
| FIRE-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie will have landing at east and lever hardware on kitchen exit for structural inspector 1/12/2004 3:31:54 PM
|
FIR03-00673
| INSP-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | FAIL |
|
|
clean up NAC panel to remove spare wires; remove covers on smoke detectors 1/12/2004 3:23:44 PM
|
FIR03-00489
| INSP-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | PASS |
|
|
|
FIR03-00075
| INSP-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | FAIL |
|
|
doors with mag locks on south exit will need to release with fire alarm; awaiting calc's for batteries as meter reading indicated higher batteries will be needed; remove all covers from smoke detectors 1/12/2004 3:27:16 PM
|