FIR03-00697
| INSP-Final Inspection | 1/9/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | A | CANC |
|
|
Troy, Here is the inspection request that you asked me to send in. We will have Randy onsite at 8:00 am on Monday. Thanks.; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
|
FIR03-00773
| INSP-Sprinkler Rough-in/Hydro | 1/9/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | A | FAIL |
|
|
Provide ceiling in the water heater room for the installation of the sprinkler pendant. Also the fire alarm panel that is monitoring the sprinkler system has a zone 7 trouble 1/12/2004 2:26:12 PM
|
FIR03-00558
| INSP-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | PART |
|
|
Second floor sprinklers are finaled in the T.I. area 1/12/2004 3:03:20 PM
|
FIR03-00794
| INSP-Sprinkler Rough-in/Hydro | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | PART |
|
|
The 24 hour air test started at 2:30 with 41 lbs. Overhead dry system is ok to cover. Riser and crawl space needs to be inspected. Contractor will provide sheet rock to separate the canopies from the main floor sprinkler system 1/12/2004 4:08:50 PM
|
BLD03-02979
| FIRE-Final Inspection | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | PASS |
|
|
life safety finaled 1/12/2004 11:43:42 AM
|
FIR03-00505
| INSP-Conference | 1/12/2004 | 1/12/2004 | 1/12/2004 12:00:00 AM | P | DONE |
|
|
I issued a citation to bill ramsey with Benchmark Electric for beginning instalation of the fire alarm system prior to having approved plans
|