Inspections for the day of: Wednesday, January 12, 2005.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00596 FIR-Aging Inspection1/12/20051/12/20051/12/2005 12:00:00 AM PASS
Still under construction 1/12/2005 10:09:25 AM
BLD04-00421 FIRE-Conference1/11/20051/12/20051/12/2005 12:00:00 AMAPART
darren ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Reviewed placement of fire extinguishers; eict signs/emergency lights are not installed; will schedule testing of alarms/life safety at one time 1/12/2005 9:16:55 AM
BLD04-01996 FIRE-Final Inspection1/11/20051/12/20051/12/2005 12:00:00 AMAPASS
justin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Need to verify address; was taken down for exterior work on west side at new door 1/12/2005 10:08:09 AM
BLD04-02630 FIRE-Final Inspection1/12/20051/12/20051/12/2005 12:00:00 AMPPASS
gary; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie There is new AHU that is under 2000 cfm per GC - detector not required; dampers installed in 1 hr ceiling 1/12/2005 3:28:47 PM
BLD04-02631 FIRE-Final Inspection1/12/20051/12/20051/12/2005 12:00:00 AMPFAIL
gary; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Fire dampers not completed in 1 hr ceiling; extinguisher needed to keep under 75 ft travel distance; per GC the AHU is under 2000 cfm so detector is not needed for AHU shutdown 1/12/2005 3:31:09 PM
BLD04-02770 FIRE-Final Inspection1/12/20051/12/20051/12/2005 12:00:00 AMPPASS
###-#### - charles Did not have ADA counter installed; final okay 1/12/2005 2:27:01 PM
FIR04-00272 INSP-Sprinkler Rough-in/Hydro1/12/20051/12/20051/12/2005 12:00:00 AMPNR
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Received ccall from Mike and this will be rescheduled 1/12/2005 1:59:54 PM
BLD03-02187 FIRE-Conference1/12/20051/12/20051/12/2005 12:00:00 AMPPART
Met with GC about the new RTU that will require a duct detector for unit shutdown as it is over 2000 cfm; there are no detectors required at the new fire dampers in 2 hr wall; will need knox box; there are different addresses that need to be updated with PDS 1/12/2005 1:58:51 PM