Inspections for the day of: Wednesday, January 12, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00762 INSP-Final Inspection1/11/20051/12/20051/12/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 1/11/2005 at 9:28:16 AM. Contact: ###-####.
FIR04-00582 INSP-Sprinkler Rough-in/Hydro1/11/20051/12/20051/12/2005 12:00:00 AMPPART
Overhead hydro test ok. Plans need to be resubmitted. Both mains are installed closer to the center of the building than shown on the plans and the tail backs are 2" instead of 1". Main out of riser room has also been rerouted. The branchline along the north wall is approx. 7'-2" off of the wall. Plans show 5'-11" 1/12/2005 12:40:29 PM
BLD04-01046 FIRE-Final Inspection1/11/20051/12/20051/12/2005 12:00:00 AMPFAIL
Repair emergency light on second floor. Provide fire extinguisher on the second floor. Provide remote annunciators for the duct smoke detectors. Provide approved door hardware for the tenant doors and provide sticker at the main exit. 1/12/2005 4:14:39 PM
FIR04-00414 INSP-Final Inspection1/12/20051/12/20051/12/2005 12:00:00 AMPPASS
Fire alarm finaled 1/12/2005 3:09:27 PM
FIR04-00783 INSP-Sprinkler Rough-in/Hydro1/12/20051/12/20051/12/2005 12:00:00 AMPFAIL
Pendant in rear classroom is overspaced. 1/12/2005 3:25:59 PM
FIR04-00785 INSP-Final Inspection1/12/20051/12/20051/12/2005 12:00:00 AMPPASS
Fire sprinklers finaled 1/12/2005 3:26:25 PM