Inspections for the day of: Thursday, January 12, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01962 FIRE-Final Inspection1/11/20061/12/20061/12/2006 5:46:10 PMPPASS
Construction meets specifications, however the Nitrogen Triflouride trailers have not been installed on the pad at this time.
BLD05-01961 FIRE-Final Inspection1/11/20061/12/20061/12/2006 5:44:18 PMPPASS
Construction meets specifications, however the Nitrogen Triflouride tube trailers have not been installed on the pad at this time.
FIR05-00608 INSP-Alarm Testing1/12/20061/12/20061/12/2006 4:30:29 PMPPASS
Fire alarm for the hood suppression system functioned properly under test conditions, inspection passed.
FIR05-00412 INSP-Final Inspection1/12/20061/12/20061/12/2006 2:21:10 PMPPASS
Corrections have been made and hood retest witnessed at a related previous inspection(no entry made at that time), permit finaled.
FIR05-00016 INSP-Final Inspection1/12/20061/12/20061/12/2006 12:39:43 PMPPASS
UG fire supply line finaled.
FIR06-00008 INSP-Sprinkler Rough-in1/12/20061/12/20061/12/2006 12:36:25 PMPPART
Overhead rough-in is acceptable for cover. No final until all ceiling tile and escutcheons are installed to facilitate heat collection and maintain the listing for the heads.
FIR05-00594 INSP-Sprinkler Rough-in1/12/20061/12/20061/12/2006 11:53:05 AMPPART
Inspected four restrooms on the first floor for overhead rough-in cover.
FIR05-00260 INSP-Final Inspection1/12/20061/12/20061/12/2006 11:48:34 AMPPASS
This was a combination inspection including an UG flush witness, overhead final inspection which was conducted while the supply was connected to the overhead, and a final alarm test. All items tested satisfactory, permit finaled.