Inspections for the day of: Thursday, January 12, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00104 INSP-Alarm Testing1/12/20061/12/20061/12/2006 4:18:47 PMPPASS
2nd floor testing passed.
FIR05-00567 INSP-Final Inspection1/12/20061/12/20061/12/2006 3:57:49 PMPPASS
Permit finaled
FIR05-00825 INSP-Final Inspection1/12/20061/12/20061/12/2006 3:32:51 PMPPASS
permit finaled
FIR05-00828 INSP-Sprinkler Rough-in/Hydro1/12/20061/12/20061/12/2006 3:31:04 PMPPASS
Sprinkler piping is ok to cover
FIR05-00664 INSP-Final Inspection1/12/20061/12/20061/12/2006 3:30:40 PMPFAIL
The duct detectors in the basement are mounted incorrectly. The fresh air must come in after the sampling tubes. Provide signage at the manual pull stations per IFC 907.4.4. Repair all exit signs and emergency lights. One smoke detector on the first floor needs relocated to be centered between the two diffusers.
FIR05-00476 INSP-Final Inspection1/12/20061/12/20061/12/2006 1:35:29 PMPPASS
Permit finaled
BLD05-02634 FIRE-Final Inspection1/11/20061/12/20061/12/2006 1:34:55 PMPCANC
Alarm problems. Inspection canceled
FIR05-00860 INSP-Final Inspection1/12/20061/12/20061/12/2006 12:55:50 PMACANC
Alarm problems. Contractor not ready.
BLD05-02146 FIRE-Final Inspection1/11/20061/12/20061/12/2006 12:52:59 PMAPASS
Life safety finaled. Per Ron Hill resubmittals are not required for the wall layout changes.
BLD04-00709 FIRE-Final Inspection1/11/20061/12/20061/12/2006 10:26:19 AMAFAIL
The cut sheet that was provided for the thumbturn locks was for "Falcon" but the manufacture of the locks is "CorbinRusswin". Need the correct cut sheet.
BLD05-01911 FIRE-Final Inspection1/11/20061/12/20061/12/2006 9:45:26 AMAPASS
life safety finaled
FIR05-00604 INSP-Sprinkler Rough-in/Hydro1/11/20061/12/20061/12/2006 9:36:41 AMAPART
Roughin for the building piping passed. Non of the riser has been inspected due to numerous items needing addressed