Inspections for the day of: Wednesday, January 12, 2011.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-01205 FIRE-Final Inspection1/6/20111/7/2011 A 
301
FIR10-00293 FIR-Aging Inspection1/12/20111/12/20111/13/2011 3:15:54 PM PEND
Ref. project related
BLD10-02764 FIRE-Final Inspection1/12/20111/12/20111/13/2011 3:08:46 PMPPART
Final pending correction notice items.
BLD10-01471 FIRE-Final Inspection1/12/20111/12/20111/13/2011 3:07:42 PMPPASS
FIR11-00003 INSP-Sprinkler Rough-in1/12/20111/12/20111/13/2011 3:07:11 PMPPART
Noted three upright heads above the womens restroom ceiling and one ssu at the riser closet yet to be replaced with QR type per scope of work, two uprights at the basement level exceed min. spacing.
BLD10-01604 FIRE-Sprinkler Rough-in1/12/20111/12/20111/13/2011 3:04:04 PMPPART
Overhead fire sprinkler work okay for cover at the grid ceiling areas.
FIR11-00003 INSP-Sprinkler Rough-in/Hydro1/11/20111/12/20111/12/2011 12:35:55 PMAPART
Overhead hydrostatic testing for the basement and first floor levels completed satisfactory.
FIR10-00528 FIR-Aging Inspection1/12/20111/12/20111/12/2011 12:21:42 PM PASS
BLD10-02486 FIRE-Conference1/11/20111/12/20111/12/2011 12:19:52 PMADONE
Regarding copy of notice on site -Maintain ceiling at the existing tenant space where modified to accomodate new wall construction. Required fire protection systems to be maintained per IFC 2006 901.4 and meet installation guidelines per NFPA 13 2007 8.1(3) regarding activation time, distribution, and area separation.
FIR10-00137 FIR-Aging Inspection1/12/20111/12/20111/12/2011 12:13:22 PM DONE
Site work in progress
BLD10-01853 FIRE-Sprinkler Rough-in1/12/20111/12/20111/12/2011 12:11:32 PMAPART
Beam clamps and seismic straps at overhead sprinkler main line hangers on the first floor okayed.
BLD10-02759 FIRE-Final Inspection1/11/20111/12/20111/12/2011 12:09:26 PMAPASS
Fire life safety inspection passed with the exception of missing suite address numbers- Contractor to post as discussed, will verify at next site visit for project related inspections.