BLD10-01205
| FIRE-Final Inspection | 1/6/2011 | 1/7/2011 | | A | |
|
|
301
|
FIR10-00293
| FIR-Aging Inspection | 1/12/2011 | 1/12/2011 | 1/13/2011 3:15:54 PM | | PEND |
|
|
Ref. project related
|
BLD10-02764
| FIRE-Final Inspection | 1/12/2011 | 1/12/2011 | 1/13/2011 3:08:46 PM | P | PART |
|
|
Final pending correction notice items.
|
BLD10-01471
| FIRE-Final Inspection | 1/12/2011 | 1/12/2011 | 1/13/2011 3:07:42 PM | P | PASS |
|
|
|
FIR11-00003
| INSP-Sprinkler Rough-in | 1/12/2011 | 1/12/2011 | 1/13/2011 3:07:11 PM | P | PART |
|
|
Noted three upright heads above the womens restroom ceiling and one ssu at the riser closet yet to be replaced with QR type per scope of work, two uprights at the basement level exceed min. spacing.
|
BLD10-01604
| FIRE-Sprinkler Rough-in | 1/12/2011 | 1/12/2011 | 1/13/2011 3:04:04 PM | P | PART |
|
|
Overhead fire sprinkler work okay for cover at the grid ceiling areas.
|
FIR11-00003
| INSP-Sprinkler Rough-in/Hydro | 1/11/2011 | 1/12/2011 | 1/12/2011 12:35:55 PM | A | PART |
|
|
Overhead hydrostatic testing for the basement and first floor levels completed satisfactory.
|
FIR10-00528
| FIR-Aging Inspection | 1/12/2011 | 1/12/2011 | 1/12/2011 12:21:42 PM | | PASS |
|
|
|
BLD10-02486
| FIRE-Conference | 1/11/2011 | 1/12/2011 | 1/12/2011 12:19:52 PM | A | DONE |
|
|
Regarding copy of notice on site -Maintain ceiling at the existing tenant space where modified to accomodate new wall construction. Required fire protection systems to be maintained per IFC 2006 901.4 and meet installation guidelines per NFPA 13 2007 8.1(3) regarding activation time, distribution, and area separation.
|
FIR10-00137
| FIR-Aging Inspection | 1/12/2011 | 1/12/2011 | 1/12/2011 12:13:22 PM | | DONE |
|
|
Site work in progress
|
BLD10-01853
| FIRE-Sprinkler Rough-in | 1/12/2011 | 1/12/2011 | 1/12/2011 12:11:32 PM | A | PART |
|
|
Beam clamps and seismic straps at overhead sprinkler main line hangers on the first floor okayed.
|
BLD10-02759
| FIRE-Final Inspection | 1/11/2011 | 1/12/2011 | 1/12/2011 12:09:26 PM | A | PASS |
|
|
Fire life safety inspection passed with the exception of missing suite address numbers- Contractor to post as discussed, will verify at next site visit for project related inspections.
|