Inspections for the day of: Monday, January 12, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03695 FIRE-Final Inspection1/12/20151/12/20151/13/2015 9:11:53 AMPFAIL
Mount fire extinguishers below 5', repair or remove eixt signs, provide sticker at the main exit, provide verification the fire alarm system is being monitored.
BLD13-03185 FIRE-Final Inspection1/12/20151/12/20151/12/2015 3:50:53 PMPFAIL
Need to provide fire dept approval on tanks, scott has approved existing fire dept access without utilizing the east side driveway, and the two emergency stop buttons along Orchard Street do not work.
FIR14-00940 INSP-Final Inspection1/9/20151/12/20151/12/2015 2:49:01 PMPCANC
Cancel per Bud. Rescheduled for tomorrow
BLD14-02186 FIRE-Final Inspection1/12/20151/12/20151/12/2015 2:45:21 PMPPASS
Life safety passed
FIR14-00596 INSP-Sprinkler Rough-in/Hydro1/12/20151/12/20151/12/2015 2:26:04 PMPPASS
Underground flush passed. Hydro not ready
FIR14-00817 INSP-Final Inspection1/12/20151/12/20151/12/2015 2:25:32 PMPFAIL
A surface mounted light is blocking a pendant sprinkler head
FIR14-00574 INSP-Sprinkler Rough-in/Hydro1/12/20151/12/20151/12/2015 12:45:38 PMPFAIL
Left message on contacts voice mail. Went to project and did not make contact. Systems are not pumped up for the requested hydro test. No inspection was performed.
FIR14-00423 INSP-Final Inspection1/12/20151/12/20151/12/2015 10:45:39 AMPPASS
Permit finaled
FIR14-00652 INSP-Final Inspection1/12/20151/12/20151/12/2015 10:45:20 AMAPASS
Permit finaled
NAF14-00006 INSP-Final1/11/20151/12/20151/12/2015 10:17:33 AMACANC
Cancel per Anthony due to notification issues.
BLD14-03144 FIRE-Final Inspection1/9/20151/12/20151/12/2015 10:16:05 AMAPASS
life safety passed
BLD14-03268 FIRE-Final Inspection1/9/20151/12/20151/12/2015 10:15:03 AMAFAIL
Repair emergency lighting or provide verification that the non-functional lighting is approved to be removed.
BLD14-03403 FIRE-Final Inspection1/9/20151/12/20151/12/2015 10:14:18 AMAPASS
Life safety passed. I noted issues with door hardware and emergency lighting with steve but since this is a vanilla finish I will not require compliance until a tenant review is done in the future.
FIR14-00182 INSP-Final Inspection1/9/20151/12/20151/12/2015 9:48:06 AMAFAIL
For todays inspection I verified audible/visuals for the first and fourth floors including live/work units. I also verified in-duct dectors on the first floor. Only two fire smoke dampers were accessible. All of the others require better access. Elevators and other items were not ready.
BLD14-02186 FIRE-Final Inspection1/9/20151/12/20151/12/2015 9:45:24 AMAFAIL
Provide annual inspection tag for the fire extinguisher and mount as discussed, remove the thumbturn dead bolt from the main exit (keyed ok) and provide sticker.