BLD14-03695
| FIRE-Final Inspection | 1/12/2015 | 1/12/2015 | 1/13/2015 9:11:53 AM | P | FAIL |
|
|
Mount fire extinguishers below 5', repair or remove eixt signs, provide sticker at the main exit, provide verification the fire alarm system is being monitored.
|
BLD13-03185
| FIRE-Final Inspection | 1/12/2015 | 1/12/2015 | 1/12/2015 3:50:53 PM | P | FAIL |
|
|
Need to provide fire dept approval on tanks, scott has approved existing fire dept access without utilizing the east side driveway, and the two emergency stop buttons along Orchard Street do not work.
|
FIR14-00940
| INSP-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 2:49:01 PM | P | CANC |
|
|
Cancel per Bud. Rescheduled for tomorrow
|
BLD14-02186
| FIRE-Final Inspection | 1/12/2015 | 1/12/2015 | 1/12/2015 2:45:21 PM | P | PASS |
|
|
Life safety passed
|
FIR14-00596
| INSP-Sprinkler Rough-in/Hydro | 1/12/2015 | 1/12/2015 | 1/12/2015 2:26:04 PM | P | PASS |
|
|
Underground flush passed. Hydro not ready
|
FIR14-00817
| INSP-Final Inspection | 1/12/2015 | 1/12/2015 | 1/12/2015 2:25:32 PM | P | FAIL |
|
|
A surface mounted light is blocking a pendant sprinkler head
|
FIR14-00574
| INSP-Sprinkler Rough-in/Hydro | 1/12/2015 | 1/12/2015 | 1/12/2015 12:45:38 PM | P | FAIL |
|
|
Left message on contacts voice mail. Went to project and did not make contact. Systems are not pumped up for the requested hydro test. No inspection was performed.
|
FIR14-00423
| INSP-Final Inspection | 1/12/2015 | 1/12/2015 | 1/12/2015 10:45:39 AM | P | PASS |
|
|
Permit finaled
|
FIR14-00652
| INSP-Final Inspection | 1/12/2015 | 1/12/2015 | 1/12/2015 10:45:20 AM | A | PASS |
|
|
Permit finaled
|
NAF14-00006
| INSP-Final | 1/11/2015 | 1/12/2015 | 1/12/2015 10:17:33 AM | A | CANC |
|
|
Cancel per Anthony due to notification issues.
|
BLD14-03144
| FIRE-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 10:16:05 AM | A | PASS |
|
|
life safety passed
|
BLD14-03268
| FIRE-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 10:15:03 AM | A | FAIL |
|
|
Repair emergency lighting or provide verification that the non-functional lighting is approved to be removed.
|
BLD14-03403
| FIRE-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 10:14:18 AM | A | PASS |
|
|
Life safety passed. I noted issues with door hardware and emergency lighting with steve but since this is a vanilla finish I will not require compliance until a tenant review is done in the future.
|
FIR14-00182
| INSP-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 9:48:06 AM | A | FAIL |
|
|
For todays inspection I verified audible/visuals for the first and fourth floors including live/work units. I also verified in-duct dectors on the first floor. Only two fire smoke dampers were accessible. All of the others require better access. Elevators and other items were not ready.
|
BLD14-02186
| FIRE-Final Inspection | 1/9/2015 | 1/12/2015 | 1/12/2015 9:45:24 AM | A | FAIL |
|
|
Provide annual inspection tag for the fire extinguisher and mount as discussed, remove the thumbturn dead bolt from the main exit (keyed ok) and provide sticker.
|