Inspections for the day of: Tuesday, January 12, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03450 Electrical Rough-In1/12/20161/12/20161/12/2016 1:54:42 PMPPASS
We would like a rough in for cover inspection please. Thank you, Dale Phone #: ###-#### Inspection requested via web by Thomas Jenkins interior walls ok cover
ELE15-04129 Rough-In Permanent Service1/12/20161/12/20161/12/2016 1:31:57 PMPPASS
Reinspect. Phone #: ###-#### Inspection requested via web by Greg Idsinga correction fixed rough-in ok cover p/s o/h n ok
ELE16-00068 Final1/12/20161/12/20161/12/2016 1:16:37 PMPCANC
Phone #: ###-#### Inspection requested via web by Erick Baker needed t/s only
ELE16-00068 Temporary Service1/12/20161/12/20161/12/2016 1:16:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Erick Baker correction fixed t/s o/h rec ok
ELE15-03274 Final1/12/20161/12/20161/12/2016 12:53:15 PMPPASS
Phone #: ###-#### Inspection requested via web by Jim Williams correction fixed final ok
ELE15-02494 Final1/11/20161/12/20161/12/2016 12:26:29 PMPPASS
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson contractor will pull a seperate permit for a/c when they are installed final ok
ELE16-00081 Final1/11/20161/12/20161/12/2016 10:43:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher final ok
ELE16-00073 Temporary Service1/11/20161/12/20161/12/2016 10:23:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE15-03150 Final1/12/20161/12/20161/12/2016 10:23:10 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Cindie Swaim Inspection cancelled from web by: Cindie Swaim
ELE16-00068 Final1/11/20161/12/20161/12/2016 10:02:00 AMAFAIL
Final temp pole Phone #: ###-#### Inspection requested via web by Erick Baker 348.12(1) FMC shall not be used in a wet location
ELE15-04048 Final1/11/20161/12/20161/12/2016 9:39:30 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan final on service change ok
ELE16-00074 Temporary Service1/11/20161/12/20161/12/2016 8:54:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin t/s u/g n ok
ELE16-00076 Temporary Service1/12/20161/12/20161/12/2016 8:46:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok