NAF15-00017
| INSP-Sprinkler Rough-in/Hydro | 1/11/2016 | 1/12/2016 | 1/12/2016 4:16:34 PM | P | PART |
|
|
Rough in fully complete. All perviously noted items completed satifactory.
Hydro Failed. Pressure dropped by 1-2 psi. Walked and found drip by upright sprinkler head in production bay. Hydro to be redone tomorrow in conjunction with final.
|
GCB15-00028
| FIRE-Final Inspection | 1/12/2016 | 1/12/2016 | 1/12/2016 2:27:09 PM | P | PASS |
|
|
Life safety completed satisfactory.
|
NAF15-00044
| INSP-Sprinkler Rough-in/Hydro | 1/12/2016 | 1/12/2016 | 1/12/2016 2:04:50 PM | P | PART |
|
|
Undergound cover for run of pipe from riser with thrust block, to just before it turns parallel to street completed satisfactory.
90 degree bend & thrust block, pipe under driveway, and tap to main still be completed.
|