Inspections for the day of: Friday, January 12, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03784 Final1/12/20181/12/20181/12/2018 3:57:56 PMPFAIL
At the end of the day if possible Phone #: ###-#### Inspection requested via web by Debby Pierce
Furniture connections shall be terminated or removed for TCO.
Circuit for millwork shall terminate in a box or wiring shall be complete once millwork in place.
210.8- Drinking fountains shall have GFCI protection.
ELE17-03763 Final1/11/20181/12/20181/12/2018 12:18:59 PMAPASS
Call Pierce for final inspection of power supplies and AV rack outlet. As close to 1130AM as possible please. Thanks Phone #: ###-#### Inspection requested via web by Rafael Castillo Final ok
ELE17-03877 Electrical Rough-In1/12/20181/12/20181/12/2018 12:18:35 PMPPART
314.16- Boxes shall have free space for all conductors enclosed in box. Displays beside each ball room entrance have 7.5 cubic in. need 11.25 minimum. Contact stated these are existing boxes however only 1 has a receptacle installed at time of inspection.
4-05-32- Code violation not to be retained.
Grid at each entrance rough in ok cover
ELE17-03763 Electrical Rough-In1/12/20181/12/20181/12/2018 12:12:05 PMPPASS
Call Pierce for final inspection of power supplies and AV rack outlet. As close to 1130AM as possible please. Thanks Phone #: ###-#### Inspection requested via web by Rafael Castillo
Circuits and power supply units for LED strip lighting for east side of exterior. Rough in ok cover
ELE16-03931 Final1/11/20181/12/20181/12/2018 11:42:22 AMAPART
6th and 7th floor corridors, stair 1, stair 2 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas noted signed off in office. Temp final ok
ELE16-03932 Final1/11/20181/12/20181/12/2018 11:41:29 AMAPART
corridors 6th and 7th floor, stair 3, stair 4 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Receptacle at bottom of stair 4 check next trip. Areas noted siged off in office. Temp final ok
ELE16-00580 Final1/11/20181/12/20181/12/2018 11:40:21 AMAPART
space 113 fire riser room, 114 bike parking, 115 generator Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted siged off in office. Temp final ok
ELE18-00144 Temporary Service1/11/20181/12/20181/12/2018 9:43:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE18-00142 Temporary Service1/11/20181/12/20181/12/2018 9:43:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE17-03127 Final1/11/20181/12/20181/12/2018 9:25:12 AMAPASS
Mucho Phone #: ###-####
Final ok