ELE17-03784
| Final | 1/12/2018 | 1/12/2018 | 1/12/2018 3:57:56 PM | P | FAIL |
|
|
At the end of the day if possible Phone #: ###-#### Inspection requested via web by Debby Pierce Furniture connections shall be terminated or removed for TCO. Circuit for millwork shall terminate in a box or wiring shall be complete once millwork in place. 210.8- Drinking fountains shall have GFCI protection.
|
ELE17-03763
| Final | 1/11/2018 | 1/12/2018 | 1/12/2018 12:18:59 PM | A | PASS |
|
|
Call Pierce for final inspection of power supplies and AV rack outlet. As close to 1130AM as possible please. Thanks Phone #: ###-#### Inspection requested via web by Rafael Castillo Final ok
|
ELE17-03877
| Electrical Rough-In | 1/12/2018 | 1/12/2018 | 1/12/2018 12:18:35 PM | P | PART |
|
|
314.16- Boxes shall have free space for all conductors enclosed in box. Displays beside each ball room entrance have 7.5 cubic in. need 11.25 minimum. Contact stated these are existing boxes however only 1 has a receptacle installed at time of inspection. 4-05-32- Code violation not to be retained. Grid at each entrance rough in ok cover
|
ELE17-03763
| Electrical Rough-In | 1/12/2018 | 1/12/2018 | 1/12/2018 12:12:05 PM | P | PASS |
|
|
Call Pierce for final inspection of power supplies and AV rack outlet. As close to 1130AM as possible please. Thanks Phone #: ###-#### Inspection requested via web by Rafael Castillo Circuits and power supply units for LED strip lighting for east side of exterior. Rough in ok cover
|
ELE16-03931
| Final | 1/11/2018 | 1/12/2018 | 1/12/2018 11:42:22 AM | A | PART |
|
|
6th and 7th floor corridors, stair 1, stair 2 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted signed off in office. Temp final ok
|
ELE16-03932
| Final | 1/11/2018 | 1/12/2018 | 1/12/2018 11:41:29 AM | A | PART |
|
|
corridors 6th and 7th floor, stair 3, stair 4 Phone #: ###-#### Inspection requested via web by Cathy Duchek Receptacle at bottom of stair 4 check next trip. Areas noted siged off in office. Temp final ok
|
ELE16-00580
| Final | 1/11/2018 | 1/12/2018 | 1/12/2018 11:40:21 AM | A | PART |
|
|
space 113 fire riser room, 114 bike parking, 115 generator Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted siged off in office. Temp final ok
|
ELE18-00144
| Temporary Service | 1/11/2018 | 1/12/2018 | 1/12/2018 9:43:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE18-00142
| Temporary Service | 1/11/2018 | 1/12/2018 | 1/12/2018 9:43:23 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE17-03127
| Final | 1/11/2018 | 1/12/2018 | 1/12/2018 9:25:12 AM | A | PASS |
|
|
Mucho Phone #: ###-#### Final ok
|