Inspections for the day of: Tuesday, January 13, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00074 INSP-Sprinkler Rough-in/Hydro1/12/20041/13/20041/13/2004 12:00:00 AMAPART
Inspection was for the closet areas on the upper floor. One pendant in the pantry will need to be relocated from over the shelving or the shelving will need to be lowered. The other closets are OK 1/13/2004 9:38:14 AM
MIS04-00007 FIR-Final1/12/20041/13/20041/13/2004 12:00:00 AMAPASS
Fire life safety finaled 1/13/2004 9:51:27 AM
FIR03-00206 INSP-Final Inspection1/12/20041/13/20041/13/2004 12:00:00 AMAFAIL
Project not ready for final inspection yet. Inspection was for covering the sprinklers in the remodeled existing area. Sprinklers are OK to cover 1/13/2004 9:33:07 AM
BLD03-02745 FIRE-Final Inspection1/12/20041/13/20041/13/2004 12:00:00 AMAPASS
Life safety for the vanilla finish is OK 1/13/2004 10:13:51 AM
BLD02-02710 FIRE-Final Inspection1/13/20041/13/20041/13/2004 12:00:00 AMPPASS
fire life safety finaled 1/13/2004 3:03:00 PM
BLD02-01060 FIRE-Final Inspection1/13/20041/13/20041/13/2004 12:00:00 AMPPASS
life safety finaled 1/13/2004 4:38:06 PM
FIR03-00273 INSP-Final Inspection1/13/20041/13/20041/13/2004 12:00:00 AMPPASS
fire alarm finaled
FIR03-00282 INSP-Final Inspection1/12/20041/13/20041/13/2004 12:00:00 AMPPASS
fire alarm system finaled 1/13/2004 1:42:28 PM
MIS03-00241 FIR-Final1/12/20041/13/20041/13/2004 12:00:00 AMPPASS
Fire life safety is OK. I signed off for Tom (structural inspector) since he was OK with his items 1/13/2004 11:41:53 AM
FIR03-00794 INSP-Sprinkler Rough-in/Hydro1/12/20041/13/20041/13/2004 12:00:00 AMPFAIL
24 hour test for the dry pipe system failed. 1/13/2004 2:42:11 PM