ELE05-02372
| ELE-Aging Inspection | 1/13/2006 | 1/13/2006 | 1/18/2006 9:50:17 AM | | DONE |
|
|
see final
|
ELE04-01984
| ELE-Aging Inspection | 1/13/2006 | 1/13/2006 | 1/17/2006 4:45:31 PM | | DONE |
|
|
see final
|
ELE05-01433
| Final | 1/13/2006 | 1/13/2006 | 1/13/2006 4:07:30 PM | P | PASS |
|
|
gilbert -call 1st before insp -re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, ok to final
|
ELE05-02371
| ELE-Aging Inspection | 1/13/2006 | 1/13/2006 | 1/13/2006 4:06:47 PM | | DONE |
|
|
see final
|
ELE05-03777
| Final | 1/13/2006 | 1/13/2006 | 1/13/2006 2:50:15 PM | P | PASS |
|
|
final on new garage Internet Inspection Request from: Andy Rose called contr, left survey, 314.25 each box shall have a cover, 430.102(B) disconnect shall be provided for air compressor
|
ELE05-04293
| Rough-In Permanent Service | 1/13/2006 | 1/13/2006 | 1/13/2006 2:33:05 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/13/2006 at 10:24:15 AM. Contact: ###-####. called contr, left corr notice,312.5 conductors entering enclosures shall have abrasion protection, 334.80 more than 2 nm cables bundled and passing thru wood framing using draft stopping shall adjust ampacity of each conductor (over panel), 300.4(A)&(D) edge of hole and nm cable shall be 11/4" from edge of framing members,BCC all make-up shall be done( #12 in wall between studs)
|
ELE06-00116
| Electrical Rough-In | 1/13/2006 | 1/13/2006 | 1/13/2006 1:03:24 PM | P | PASS |
|
|
underground insp - mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g for conduit south side bldg ok to cover.
|
ELE06-00130
| Rough-In Permanent Service | 1/12/2006 | 1/13/2006 | 1/13/2006 10:31:38 AM | A | PASS |
|
|
###-#### allen called contr, left survey, 312.5 conductors entering enclosures shall have abrasion protection, 430.107 pump motor disconnect in tub shall be readily accessible
|
ELE05-04651
| Electrical Rough-In | 1/12/2006 | 1/13/2006 | 1/13/2006 10:20:17 AM | A | PASS |
|
|
jeremy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa walls ok to cover, hard lid ceiling ok to cover
|
ELE06-00097
| Rough-In Permanent Service | 1/12/2006 | 1/13/2006 | 1/13/2006 9:54:23 AM | A | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ric ok, p/s u/g n ok
|
ELE05-03168
| Final | 1/12/2006 | 1/13/2006 | 1/13/2006 9:32:41 AM | A | PASS |
|
|
code= 2241; Phone #: ###-#### Internet Inspection Request from: William Zerfas called contr to finish tub access. ok to final
|
ELE06-00116
| Electrical Rough-In | 1/12/2006 | 1/13/2006 | 1/13/2006 9:27:12 AM | A | PASS |
|
|
grounding inspection//mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa gec only ok to backfill
|
ELE06-00139
| Electrical Rough-In | 1/12/2006 | 1/13/2006 | 1/13/2006 9:25:43 AM | A | PASS |
|
|
dave -for partial ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie halo room only ok to cover
|
ELE05-02371
| Final | 1/13/2006 | 1/13/2006 | 1/13/2006 12:00:00 AM | P | PASS |
|
|
looked at sign, ok to final
|