Inspections for the day of: Thursday, January 13, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02469 ELE-Aging Inspection1/13/20111/13/20111/13/2011 3:33:45 PM DONE
see final
ELE10-02469 Final1/13/20111/13/20111/13/2011 3:33:31 PMPPASS
ok
ELE10-02470 ELE-Aging Inspection1/13/20111/13/20111/13/2011 3:31:40 PM DONE
suc
ESC10-00497 General Inspection1/13/20111/13/20111/13/2011 3:21:57 PMPPASS
jnstalling sprinklers, looked ok
ESC10-00777 General Inspection1/13/20111/13/20111/13/2011 3:04:23 PMAPASS
doing drive, looked ok
ELE10-02121 Final1/13/20111/13/20111/13/2011 2:45:22 PMPPART
call first Phone #: ###-#### >> Inspection requested via web by PAT MILLER receptacles ok, will do lighting later
ELE11-00078 Electrical Rough-In1/13/20111/13/20111/13/2011 1:51:52 PMPPASS
rocky Phone #: ###-#### ri ok
ELE10-01904 Final1/12/20111/13/20111/13/2011 12:52:08 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Josh Craig ok final
ELE10-02584 Final1/12/20111/13/20111/13/2011 10:24:43 AMAPASS
Garage code 1357 Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ok final
ELE10-02758 Electrical Rough-In1/12/20111/13/20111/13/2011 9:37:21 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left message, left correction notice, NEC 334.30 shall staple nm cable within 12" of box, 210.52(B) small appliance branch circuits shall be on 20A circuits, 210.8(A)(7) shall provide gfci protection within 6' of sinks
GCE11-00009 GCE-Temporary Service1/12/20111/13/20111/13/2011 8:56:04 AMAFAIL
Scope: Temp ServiceContact: Jeremy @ ###-#### called, left correction notice, NEC 408.4 shall provide circuit schedule, 312.5 shall provide abrasion protection, 110.14(A) shall tighten terminations, 230.71(B) shall provide suitable handle tie at trailer main, 400.5 shall provide minimum #4 flexible cord for 60A main and trailer service, 400.10 shall provide strain relief for cords at fittings, 400.14 shall protect cable from damage, BCC shall provide job id sticker