Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00643 INSP-Final Inspection1/13/20111/13/20111/13/2011 4:08:31 PMPPASS
permit finaled
BLD11-00056 FIRE-Conference1/13/20111/13/20111/13/2011 4:07:25 PMPFAIL
Repair all exit signs/emergency lights. Provide additional exit signs, as per plans, for secondary egress from second floor. Remove dead bolt from second floor exit door. If door to warehouse fom second floor is installed, provide lever hardware. Provide single action hardware on double doors from warehouse. Provide annual inspection for all fire extinguishers. Provide annual inspection for fire sprinkler system. Repare fire alarm system.
FIR10-00028 INSP-Final Inspection1/13/20111/13/20111/13/2011 3:58:04 PMPCANC
Canceled due to time constraints and Micron plan review
FIR10-00144 INSP-Final Inspection1/13/20111/13/20111/13/2011 3:57:14 PMPCANC
Canceled due to time constraints and Micron plan review
BLD10-02683 FIRE-Final Inspection1/12/20111/13/20111/13/2011 3:09:09 PMAFAIL
Provide sticker and indicator at the exterior double door as discussed.
FIR10-00579 INSP-Sprinkler Rough-in1/12/20111/13/20111/13/2011 12:16:30 PMAPASS
The piping in the main/front canopy can be covered. See the city approved plans for location with todays date.
FIR10-00658 INSP-Final Inspection1/11/20111/13/20111/13/2011 10:43:44 AMAFAIL
Provide building map as per note 19, provide knox box per note 20, adjust the backflow tamper switch and retest, provide the correct orfice in the inspectors test and test flow switch.
BLD10-02170 FIRE-Final Inspection1/12/20111/13/20111/13/2011 10:34:06 AMAPASS
Life safety passed
FIR10-00548 INSP-Final Inspection1/12/20111/13/20111/13/2011 10:32:23 AMAPASS
permit finaled