Inspections for the day of: Friday, January 13, 2012.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02884 FIRE-Alarm Testing1/13/20121/13/20121/13/2012 4:19:43 PMAPASS
BLD11-01901 FIRE-Final Inspection1/13/20121/13/20121/13/2012 4:17:50 PMAPASS
BLD11-02603 FIRE-Final Inspection1/11/20121/13/20121/13/2012 4:17:30 PMPPASS
PFE at the mezzanine level and a current tag at the office extinguisher to be provided prior to structural final as agreed. Life safety passed.
FIR11-00524 INSP-Sprinkler Rough-in/Hydro1/12/20121/13/20121/13/2012 3:00:06 PMPFAIL
Rough-in inspection completed for system # 4 clean link and photo bay. Noted items include missing retainers at several beam clamps on branchlines, 4" and 6" mains, missing hanger at arm-over, pendent heads are blocked or obstructed at numerous locations due to proximity to AMH brackets, flex head whips are not yet installed at various areas in the clean link, missing seismic bracing at the 6" main, secure EQ brace at the 4" main, added 90s at branchlines in the photo bay are not included in the calcs.- branch line restraint at these locations shall be provided per NFPA 13 9.3.6.4.