BLD13-02810
| FIRE-Final Inspection | 1/13/2014 | 1/13/2014 | 1/13/2014 3:48:12 PM | P | FAIL |
|
|
Provide exit signs and exit discharge lighting as per the approved plans
|
FIR13-00671
| INSP-Final Inspection | 1/13/2014 | 1/13/2014 | 1/13/2014 3:46:46 PM | P | FAIL |
|
|
Provide correct netcon for the transmitter, provide signage on door, repair outside alarm bell, repair the smoke dampers, provide map at the FACP, provide/finish installing the mag lock system...ect. See city approved plans for complete list.
|
FIR13-00569
| INSP-Final Inspection | 1/13/2014 | 1/13/2014 | 1/13/2014 2:21:43 PM | P | FAIL |
|
|
The exterior alarm bell needs to be repaired. All other items appear ok.
|
BLD13-02515
| FIRE-Conference | 1/10/2014 | 1/13/2014 | 1/13/2014 2:19:22 PM | A | DONE |
|
|
Bob and I discussed the new office partitions obstruction of the ceiling mounted audio/visual devices.
|
BLD13-02637
| FIRE-Final Inspection | 1/10/2014 | 1/13/2014 | 1/13/2014 8:28:33 AM | A | PASS |
|
|
Life safety passed
|