ELE14-01182
| Electrical Rough-In | 1/13/2015 | 1/13/2015 | 1/13/2015 3:09:25 PM | P | PASS |
|
|
Ceiling inspection. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Ceiling cover, light fixture change out, ok to cover
|
ELE15-00031
| Permanent Service | 1/13/2015 | 1/13/2015 | 1/13/2015 1:10:50 PM | P | PASS |
|
|
Bill-would like as close to 1 as possible Phone #: ###-#### PS, OH, RC, OK
|
ELE15-00079
| Final | 1/13/2015 | 1/13/2015 | 1/13/2015 12:58:55 PM | P | PASS |
|
|
Please call so we can get you in Phone #: ###-#### Inspection requested via web by Eddy Udry Added subpanel next to meter main to allow for added circuits in the kitchen . Final OK
|
ELE14-03416
| Electrical Rough-In | 1/13/2015 | 1/13/2015 | 1/13/2015 12:20:18 PM | P | PASS |
|
|
Inspection for the basement. Please call if no one is there. Thanks, Dustin Phone #: ###-#### Inspection requested via web by Dustin Kuester RI Basement, OK to cover
|
ELE14-03068
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 10:48:45 AM | A | PASS |
|
|
Corrections completed. Thanks Phone #: ###-#### Inspection requested via web by Randy Fletcher Corrections have been made, ok to allow floor heat per Daryl DeGrange. Final OK
|
ELE14-01910
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 10:22:33 AM | A | FAIL |
|
|
Call Tim if any problems
Key is above the small window on the front porch Phone #: ###-#### Inspection requested via web by John Harvey left notice with building contractor 210.8A 2 GFI protection required, all receptacles in garage 210.8A7 GFI protection require all receptacles within 6 foot of sink 334.12 NM calbe not permitted in wet locations 422.31 Disconnecting means required for all permanently installed appliances 210.52 C 3 Penninsula receptacle required 356.30 LFNC shall be secured within 12 inches of boxes 408.4 Circuit directory shall be legibly marked 110.3 B Installation and use, items shall be installed according to instructions, fllor heat thermostat not functioning, could not test GFI
|
ELE15-00076
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 9:25:35 AM | A | CANC |
|
|
Builder to unlock in AM. Phone #: ###-#### Inspection requested via web by Paula Gratiot cancelled, see rough in inspection
|
ELE15-00076
| Electrical Rough-In | 1/13/2015 | 1/13/2015 | 1/13/2015 9:25:15 AM | P | PASS |
|
|
Builder to unlock in AM. Phone #: ###-#### Inspection requested via web by Paula Gratiot Outlets on and around added fireplace, OK to cover
|
ELE15-00075
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 9:01:01 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher called contractor 210.12 A Arc fault protection requried, dwelling unit bedrooms, smoke detector and light switch relocated into bedroom, need arc fault on those items
|
ELE15-00036
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 8:35:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt corrections made, Final OK
|