Inspections for the day of: Tuesday, January 13, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01182 Electrical Rough-In1/13/20151/13/20151/13/2015 3:09:25 PMPPASS
Ceiling inspection. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Ceiling cover, light fixture change out, ok to cover
ELE15-00031 Permanent Service1/13/20151/13/20151/13/2015 1:10:50 PMPPASS
Bill-would like as close to 1 as possible Phone #: ###-####
PS, OH, RC, OK
ELE15-00079 Final1/13/20151/13/20151/13/2015 12:58:55 PMPPASS
Please call so we can get you in Phone #: ###-#### Inspection requested via web by Eddy Udry
Added subpanel next to meter main to allow for added circuits in the kitchen . Final OK
ELE14-03416 Electrical Rough-In1/13/20151/13/20151/13/2015 12:20:18 PMPPASS
Inspection for the basement. Please call if no one is there. Thanks,
Dustin Phone #: ###-#### Inspection requested via web by Dustin Kuester
RI Basement, OK to cover
ELE14-03068 Final1/12/20151/13/20151/13/2015 10:48:45 AMAPASS
Corrections completed. Thanks Phone #: ###-#### Inspection requested via web by Randy Fletcher
Corrections have been made, ok to allow floor heat per Daryl DeGrange.
Final OK
ELE14-01910 Final1/12/20151/13/20151/13/2015 10:22:33 AMAFAIL
Call Tim if any problems

Key is above the small window on the front porch Phone #: ###-#### Inspection requested via web by John Harvey
left notice with building contractor
210.8A 2 GFI protection required, all receptacles in garage
210.8A7 GFI protection require all receptacles within 6 foot of sink
334.12 NM calbe not permitted in wet locations
422.31 Disconnecting means required for all permanently installed appliances
210.52 C 3 Penninsula receptacle required
356.30 LFNC shall be secured within 12 inches of boxes
408.4 Circuit directory shall be legibly marked
110.3 B Installation and use, items shall be installed according to instructions, fllor heat thermostat not functioning, could not test GFI
ELE15-00076 Final1/12/20151/13/20151/13/2015 9:25:35 AMACANC
Builder to unlock in AM. Phone #: ###-#### Inspection requested via web by Paula Gratiot
cancelled, see rough in inspection
ELE15-00076 Electrical Rough-In1/13/20151/13/20151/13/2015 9:25:15 AMPPASS
Builder to unlock in AM. Phone #: ###-#### Inspection requested via web by Paula Gratiot
Outlets on and around added fireplace, OK to cover
ELE15-00075 Final1/12/20151/13/20151/13/2015 9:01:01 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Fletcher
called contractor
210.12 A Arc fault protection requried, dwelling unit bedrooms, smoke detector and light switch relocated into bedroom, need arc fault on those items
ELE15-00036 Final1/12/20151/13/20151/13/2015 8:35:28 AMAPASS
Phone #: ###-#### Inspection requested via web by John VanZandt
corrections made, Final OK