FIR14-00182
| INSP-Alarm Testing | 1/12/2015 | 1/13/2015 | 1/13/2015 4:33:26 PM | A | NR |
|
|
Mag locks at exit doors failed to release upon general alarm condition.
|
FIR14-00917
| INSP-Final Inspection | 1/13/2015 | 1/13/2015 | 1/13/2015 4:28:27 PM | P | PART |
|
|
Rough-in inspection passed. Cover approval pending tenting insp.
|
BLD12-02886
| FIRE-Alarm Testing | 1/12/2015 | 1/13/2015 | 1/13/2015 2:39:56 PM | A | PART |
|
|
Kent Phone #: ###-####
|
FIR14-00901
| INSP-Sprinkler Rough-in | 1/13/2015 | 1/13/2015 | 1/13/2015 2:39:04 PM | P | PART |
|
|
A plan modification will be necessary due to significant changes in the field installation from original design.
|
FIR14-00437
| INSP-Sprinkler Rough-in | 1/12/2015 | 1/13/2015 | 1/13/2015 2:37:05 PM | P | PART |
|
|
Begin 24 hr air test of the new dry system -2:00PM@ 43 psig.
|
BLD14-03001
| FIRE-Final Inspection | 1/12/2015 | 1/13/2015 | 1/13/2015 2:33:29 PM | P | NR |
|
|
Items noted include; missing ceiling tile at open office 124 and work room 113, need to repair EM light at hall 102, repair exit sign/EM light at both the east and west exit doors, exit sign at open office 107 does not operate on backup power source. Remainder of life safety inspection items okayed.
|
FIR14-00844
| INSP-Final Inspection | 1/12/2015 | 1/13/2015 | 1/13/2015 2:29:19 PM | P | NR |
|
|
Missing field ceiling tile at several locations including work room 113 and open office 124, some escutcheons are not installed.
|
FIR14-00182
| INSP-Sprinkler Rough-in/Hydro | 1/12/2015 | 1/13/2015 | 1/12/2015 4:49:27 PM | A | CANC |
|
|
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Monday, January 12, 2015.
|