MEC15-00082
| Rough-in | 1/13/2015 | 1/13/2015 | 1/13/2015 4:36:37 PM | P | PASS |
|
|
Oleg Phone #: ###-####
|
MEC15-00150
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 4:03:37 PM | P | PASS |
|
|
Installer Scott ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich
|
MEC14-05070
| Rough-in | 1/13/2015 | 1/13/2015 | 1/13/2015 3:38:46 PM | P | PART |
|
|
Upstairs - Hard Lid inspection Contact Curt with any questions. 208.412.6685 Phone #: ###-#### Inspection requested via web by Bailey Esposito - elevator equipment ceiling okay to cover
|
MEC14-05747
| Final | 1/13/2015 | 1/13/2015 | 1/13/2015 3:10:58 PM | P | FAIL |
|
|
Outside unit only changed out air conditioning to heat pump Inspection requested via web by MARGIE ROWE - need water tight electrical flex between disconnect and heat pump
|
MEC14-05632
| Rough-in | 1/13/2015 | 1/13/2015 | 1/13/2015 2:35:59 PM | P | FAIL |
|
|
Bj 5730755 Inspection requested via web by william kerwin - need insulation shield on b-vent for water heater, missing a 6" supply in master bath w/c
|
MEC14-05632
| Pressure Test | 1/13/2015 | 1/13/2015 | 1/13/2015 2:31:57 PM | P | PASS |
|
|
Bj 5730755 Inspection requested via web by william kerwin - 20lb gas, 5lb flue pass
|
MEC14-03522
| Final | 1/13/2015 | 1/13/2015 | 1/13/2015 2:03:09 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Troy Worley - air balance report shows zero cfm on second test for bedroom #2
|
MEC14-03829
| Final | 1/13/2015 | 1/13/2015 | 1/13/2015 1:54:35 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Worley
|
MEC15-00155
| Rough-in | 1/13/2015 | 1/13/2015 | 1/13/2015 1:51:23 PM | P | PASS |
|
|
Fireplace rough in pass
|
MEC15-00084
| Rough-in | 1/13/2015 | 1/13/2015 | 1/13/2015 1:23:35 PM | P | PASS |
|
|
Oleg Phone #: ###-#### - 5lb flue, rough in pass
|
MEC15-00148
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 10:26:37 AM | P | PASS |
|
|
installer Sam ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich
|
MEC15-00084
| Rough-in | 1/12/2015 | 1/13/2015 | 1/13/2015 10:08:37 AM | A | FAIL |
|
|
Oleg-late AM if possible Phone #: ###-#### - 5lb flue fail on smaller furnace
|
MEC15-00124
| Final | 1/13/2015 | 1/13/2015 | 1/13/2015 9:46:52 AM | A | PASS |
|
|
|
MEC14-05305
| Final | 1/12/2015 | 1/13/2015 | 1/13/2015 9:17:06 AM | A | FAIL |
|
|
Sarah or Randy Phone #: ###-#### - Need to install vent duct to out doors on range hood, or install a recirculation kit for range hood.
|
MEC15-00082
| Rough-in | 1/12/2015 | 1/13/2015 | 1/13/2015 8:57:15 AM | A | FAIL |
|
|
oleg Phone #: ###-#### - need 6" fresh air to return air plenum
|