ELE16-01838
| Final | 1/12/2017 | 1/13/2017 | 1/13/2017 1:54:39 PM | A | PART |
|
|
Call Tom Hartung for final inspection of levels 1 through 4 stack 2 Office. Phone #: ###-#### Inspection requested via web by Tom Betty Will check items noted for Annex on 11-22-16 in future. Area noted OK occupy
|
ELE15-01348
| Final | 1/12/2017 | 1/13/2017 | 1/13/2017 1:44:32 PM | A | PART |
|
|
Call Tom Hartung for levels 1 through 4 Office building final inspection of requested via web by Tom Betty Discussed if a handle of buss duct disconnects were required at each floor for disconnects located above 6'7". 368.17(C)- States where such devices are mounted out of reach and contain a disconnecting means, suitable means such as chains, ropes, or sticks shall be provided for operating disconnecting means from floor. 240.24 Overcurrent devices location on premises. Overcurrent devices shall be readily accessible and shall be installed so that the grip of the operating handle at its highest point is not more than 6'7" above floor or platform. 404.8 Switches accessiblity. Same wording handle at its highest point shall not exceed 6'7". At future date will check handles are in place due to someone keeps removing them and not returning to areas needed. Fountain located on level 1 northwest corner, shall check for drain in equipment room, and GFCI protection located in fountain control panel, unable to test not energized waiting for water. Equipotential bond, luminaire clearance not rquired due to decorative body of water. All wiring, boxes located below raised floor exposed to water redone to ensure good electrical connections. Replacing gear west end due to flood over weekend. Will call for inspection when complete. Call stations on these levels installed. Areas noted levels 1 thru 4 stack 2 flood areas OK to occupy
|
ELE17-00068
| Final | 1/12/2017 | 1/13/2017 | 1/13/2017 10:48:04 AM | A | CANC |
|
|
Pole near parking lot Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON Needed permanent service inspection.
|
ELE17-00068
| Permanent Service | 1/13/2017 | 1/13/2017 | 1/13/2017 10:47:43 AM | P | FAIL |
|
|
Pole near parking lot Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON 110.24- Available fault current shall be posted priot to permanent service inspection.
|
ELE14-00019
| Final | 1/12/2017 | 1/13/2017 | 1/13/2017 10:15:47 AM | A | PASS |
|
|
this permit needs to be finaled for the c of o-final was orignally cancelled-no one called it in-I''m just hoping you can see if it''s good Candy Floor heat inspected on permit ELE14-00656. Final ok
|
ELE16-03560
| Final | 1/12/2017 | 1/13/2017 | 1/13/2017 10:14:50 AM | A | FAIL |
|
|
Code to get in 3162 Phone #: ###-#### Inspection requested via web by Robert Murray 110.3- Garage circuit not complete. Opener receptacle still temp receptacle installed. GFI works other do not. 210.52-Receptacles located in cabinets do not count for general receptacle layout. Add receptacles on each side of entertainment cabinet 24" or greater walls. 356.30- Flexible non metallic conduit installed in island shall be secured with in 12" of a box and 6' intervals. 410.16- Master closet luminaire has standard screw shall with LED lamp shall have 12" clearance from storage shelf.
|
ELE16-03221
| Final | 1/12/2017 | 1/13/2017 | 1/13/2017 8:37:49 AM | A | PASS |
|
|
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Final ok
|
ELE16-03221
| Electrical Rough-In | 1/13/2017 | 1/13/2017 | 1/13/2017 8:37:41 AM | P | PASS |
|
|
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Listing and disconnecting means confirmed. Rough in ok
|