Inspections for the day of: Friday, January 13, 2017.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00041 Permanent Service1/12/20171/13/20171/13/2017 2:20:12 PMPPASS
Elderly couple service change
Need power same day.
Late afternoon inspection preferred Phone #: ###-#### Inspection requested via web by David McClellan
p/s o/h rec ok
ELE16-02600 Electrical Rough-In1/13/20171/13/20171/13/2017 1:04:27 PMPPASS
Please come close to 12:00 if possible. Level 6 penthouses, level 4, and level 2/3 bathroom re-inspection. Matt Mouser is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
6th floor penthouses walls and hard lids ok cover
ELE16-02600 Final1/13/20171/13/20171/13/2017 1:04:21 PMPPART
Please come close to 12:00 if possible. Level 6 penthouses, level 4, and level 2/3 bathroom re-inspection. Matt Mouser is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
FLoors 1 thru 4 temp occ only ok(verified corrections in baths and remaining light boxes and type mc whips safe ended)
ELE16-03417 Final1/13/20171/13/20171/13/2017 11:52:21 AMPPASS
Reinspection Phone #: ###-#### Inspection requested via web by Andrea Creek
Corrections fixed final ok
ELE16-03418 Final1/13/20171/13/20171/13/2017 11:51:44 AMPPASS
Reinspection Phone #: ###-#### Inspection requested via web by Andrea Creek
Corrections fixed final ok
ELE16-03937 Final1/13/20171/13/20171/13/2017 11:39:15 AMPPASS
Ready for final. Please contact Jason at ###-#### in route for access. Phone #: ###-#### Inspection requested via web by Kelly Felin
Final for up bath and bed ok
ELE16-04085 Electrical Rough-In1/12/20171/13/20171/13/2017 11:09:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Dinaing room B ceilings only ok cover
ELE16-03418 Final1/12/20171/13/20171/13/2017 10:42:32 AMAFAIL
Phone #: ###-#### Inspection requested via web by Andrea Creek
Down bath in-op
ELE16-03417 Final1/12/20171/13/20171/13/2017 10:42:12 AMAFAIL
Phone #: ###-#### Inspection requested via web by Andrea Creek
406 All 120v receptacles shall be tamper resistant (back patio)
352.12 PVC shall be supported within 36" of a box
ELE16-03537 Final1/12/20171/13/20171/13/2017 10:03:20 AMAPASS
key is in a 1/2 inch pvc lb on top of weatherproof next to front door Phone #: ###-#### Inspection requested via web by kevin blackmon
Final ok
ELE16-03297 Final1/12/20171/13/20171/13/2017 9:16:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga
Final ok
ELE16-03297 Electrical Rough-In1/13/20171/13/20171/13/2017 9:16:23 AMPPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga
Back area ceilings only ok cover all other lights were existing and not touched
ELE16-03572 Rough-In Permanent Service1/12/20171/13/20171/13/2017 8:54:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Schroder
Rough-in ok cover p/s u/g n ok