FIR19-00703
| INSP-Sprinkler Rough-in | 1/13/2020 | 1/13/2020 | 1/13/2020 3:34:46 PM | P | PART |
|
|
Rough to cover inspection for remaining level 5 overhead fire sprinkler piping complete, level 5 approved for cover.
Mike Phone #: ###-####
|
FIR20-00020
| INSP-Final Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 3:34:02 PM | P | PART |
|
|
Rough to cover inspection for stub up and approximately 8 feet of pipe from footing complete, piping inspected approved for cover, remainder of piping to be installed at a later date.
Underground inspection for cover. Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
BLD19-00727
| FIRE-Final Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 3:32:36 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for area of work complete.
|
FIR20-00010
| INSP-Final Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 3:31:52 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
|
BLD19-03974
| FIRE-Final Inspection | 1/10/2020 | 1/13/2020 | 1/13/2020 12:24:44 PM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
AJ Phone #: ###-####
|
FIR18-00224
| INSP-Final Inspection | 1/10/2020 | 1/13/2020 | 1/13/2020 12:00:21 PM | A | PASS |
|
|
Final inspection for AES communicator complete.
Please check in at School office. District and alarm personnel will be on site. Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
BLD19-02053
| FIRE-Final Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 11:32:54 AM | P | CANC |
|
|
Cancelled per conversation with point of contact, will be requested for a later date.
ronald Phone #: ###-####
|
FIR20-00020
| INSP-Final Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 11:14:40 AM | P | CANC |
|
|
Please call Chris Ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|
FIR19-00601
| INSP-Sprinkler Rough-in | 1/12/2020 | 1/13/2020 | 1/13/2020 11:05:23 AM | A | FAIL |
|
|
Appears that no corrections to tenting have been made, reference notes entered on the 09JAN2020 inspection.
Tenting. Call James when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR17-00178
| INSP-Final Inspection | 1/10/2020 | 1/13/2020 | 1/13/2020 10:37:10 AM | A | FAIL |
|
|
Overspaced audio visual devices in electrical room area, section 10 area 90. Notated city approved draiwngs areas where candella setting was incorrect, inspection was stopped after 6 deficiencies.
Dillion Phone #: ###-####
|
BLD19-03650
| FIRE-Conference | 1/10/2020 | 1/13/2020 | 1/13/2020 9:04:53 AM | A | DONE |
|
|
Fire conference complete, discussed temporary install of elevator lobby doors due to finish doors being on order, advised point of contact to discuss with structural, if no issue with structural inspector then doors/frames can be used for temp.
Zach Phone #: ###-####
|