Inspections for the day of: Monday, January 14, 2008.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02761 FIRE-Final Inspection1/11/20081/14/20081/14/2008 5:09:07 PMAPASS
Fire life safety passed.
FIR07-00957 INSP-Final Inspection1/14/20081/14/20081/14/2008 5:06:31 PMPPASS
Corrections verified for compliance, fire sprinkler permit finaled.
FIR07-00944 INSP-Supply line flush1/14/20081/14/20081/14/2008 5:05:49 PMPPASS
Field inspection passed.
FIR07-00944 INSP-Final Inspection1/14/20081/14/20081/14/2008 4:59:46 PMPPASS
Fire sprinkler permit finaled.
BLD07-00994 FIRE-Conference1/14/20081/14/20081/14/2008 4:31:38 PMPDONE
Conference completed.Look at old sky lights that are no longer in use before closing up.no Sprinklers required.
BLD08-00010 FIRE-Final Inspection1/14/20081/14/20081/14/2008 3:56:39 PMPFAIL
Items needing repair,Main front exit door needs approved automatic flush bolts.A sign over front door (this door to remain unlocked when building is occupied.Door handles in the building need to comply with (IFC 1008.1.8.1) remove bolt locks on wharehouse doors and change to comply to the IFC above.Repair exit lights and and emergency lights.KR
FIR07-00994 INSP-Final Inspection1/10/20081/14/20081/14/2008 3:04:28 PMPPASS
Work is completed. KR
FIR06-00540 INSP-Sprinkler Rough-in/Hydro1/14/20081/14/20081/14/2008 2:43:10 PMACANC
daryl - ###-####
FIR07-00695 INSP-Final Inspection1/14/20081/14/20081/14/2008 2:41:03 PMPFAIL
Visible leakage noted at the riser main control valve, missing one DSW head at the garage, one pendent head at the foyer is not installed, two heads at a hallway are overspaced, inspection concluded at this time due to the number of defficient items found at the start, project is not ready for final at this time.
FIR08-00005 INSP-Final Inspection1/11/20081/14/20081/14/2008 2:05:47 PMPNR
Fire alarm permit needs to be called in at the same time for inter connection to hood system. KR
FIR07-00489 INSP-Final Inspection1/11/20081/14/20081/14/2008 1:52:17 PMAPART
See approved set of plans of devices tested. KR
FIR07-00764 FIR-Aging Inspection1/14/20081/14/20081/14/2008 1:30:53 PM DEFR
wip
FIR06-00727 INSP-Sprinkler Rough-in1/14/20081/14/20081/14/2008 1:30:21 PMPCANC
Wrong permit number called in for inspection.
FIR07-00148 INSP-Final Inspection1/11/20081/14/20081/14/2008 1:27:13 PMAPASS
Final inspection passed, FP permit finaled.
FIR07-00143 INSP-Final Inspection1/11/20081/14/20081/14/2008 1:26:07 PMAPASS
Fire sprinkler work passed final inspection, permit finaled.
FIR07-00146 INSP-Final Inspection1/11/20081/14/20081/14/2008 1:25:07 PMAPASS
Required corrections have been made, as-builts accepted, fire sprinkler permit finaled.
BLD08-00001 FIRE-Final Inspection1/11/20081/14/20081/14/2008 10:42:11 AMAFAIL
See seven item correction notice left on site for a list of defficiencies including door hardware at four locations, repair EM lighting, install cover at open j-box, missing two max. occupant load signs, post one PFE, provide an additional exit sign per plan review annotations, post signage at the main exit from the basement club area, see building plan review notes for general requirements.
BLD07-02426 FIRE-Final Inspection1/11/20081/14/20081/14/2008 10:03:57 AMAPASS
Fire life safety completed. KR
FIR07-00962 INSP-Final Inspection1/11/20081/14/20081/14/2008 9:18:07 AMAPASS
Corrections were made per last inspection. KR
FIR07-00974 INSP-Final Inspection1/11/20081/14/20081/14/2008 8:49:30 AMAPASS
Fire alarm work completed acceptable, field inspection passed, permit finaled.
BLD07-01386 FIRE-Final Inspection1/11/20081/14/20081/14/2008 8:48:24 AMAPASS
Knox box to be provided as discussed, need to complete one small area missing gyp. board install at the future elevator shaft for fire rating prior to structural inspection, remainder of building shell permit life safety is satisfactory.
BLD07-02015 FIRE-Final Inspection1/11/20081/14/20081/14/2008 8:44:15 AMAPASS
Items on previous c/n are finished, one exit sign repaired while on site, fire life safety passed.
FIR07-00913 INSP-Final Inspection1/12/20081/14/20081/14/2008 8:43:02 AMAPASS
Necessary corrections have been completed, fire sprinkler permit finaled.
FIR07-00994 INSP-Final Inspection1/9/20081/14/20081/9/2008 10:50:54 AMACANC
Scheduled by a contractor via Hello! on 1/9/2008 at 10:28:07 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 9 2008 10:50AM.