Inspections for the day of: Monday, January 14, 2013.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00521 FIR-Aging Inspection1/14/20131/14/20131/15/2013 3:08:01 PM NR
FIR12-00557 INSP-Final Inspection1/14/20131/14/20131/14/2013 3:58:50 PMPFAIL
For todays inspection we verified strobe spacing in the high ceiling areas. At the east end of the building Rand and I agreed that relocating one strobe in the low ceiling area will provide coverage in another high ceiling area. That work was performed as I waited. The smoke detectors were tested as well. However no signals were received at the monitoring station. To final this project signals need to be received, as-builts provided, map at the facp.
FIR12-00728 INSP-Final Inspection1/11/20131/14/20131/14/2013 1:44:42 PMAPASS
Permit finaled
FIR12-00637 INSP-Supply line flush1/11/20131/14/20131/14/2013 1:08:19 PMAPASS
Underground flush passed.
BLD10-02541 FIRE-Final Inspection1/11/20131/14/20131/14/2013 10:06:43 AMAPASS
Life safety passed