ELE09-01597
| ELE-Aging Inspection | 1/14/2013 | 1/14/2013 | 1/14/2013 2:54:46 PM | | DONE |
|
|
Electrical contractor will contact owner for progress report of needed material to complete equipment requirements
|
ELE12-03059
| Final | 1/14/2013 | 1/14/2013 | 1/14/2013 1:57:26 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by cory carman final ok
|
ELE13-00004
| Rough-In Permanent Service | 1/14/2013 | 1/14/2013 | 1/14/2013 1:35:05 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-in p/s u/g n ok meter pac
|
ELE13-00075
| Electrical Rough-In | 1/13/2013 | 1/14/2013 | 1/14/2013 1:13:29 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC 300.4 Nail plates needed, Restaple NM cable that is within 1 1/4 in. of framing member edge NEC 334.30 NM cable shall be stapled within 12 in. of every outlet box and service panel. NEC 210.52 Outside outlet (Front of house were wall is open)
|
ELE12-03025
| Final | 1/14/2013 | 1/14/2013 | 1/14/2013 12:09:01 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI final ok
|
ELE12-00179
| ELE-Request for Extension | 1/11/2013 | 1/14/2013 | 1/14/2013 9:45:50 AM | A | PASS |
|
|
Brandi Houle Phone #: ###-#### Homeowner wants to start electrical install in spring after scheduling conferance meeting, Extenion ok
|
ELE13-00051
| Electrical Rough-In | 1/14/2013 | 1/14/2013 | 1/14/2013 9:42:50 AM | P | PASS |
|
|
Please call jared if any questons Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL rough-in ok cover bathroom addition in warehouse
|
ELE12-01131
| Final | 1/11/2013 | 1/14/2013 | 1/14/2013 9:26:23 AM | A | PASS |
|
|
Brian Phone #: ###-#### corrections done final ok
|
ELE13-00073
| Final | 1/11/2013 | 1/14/2013 | 1/14/2013 8:57:45 AM | A | CANC |
|
|
Please Final this. Thanks!!! Dan Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
|
ELE13-00073
| Electrical Rough-In | 1/11/2013 | 1/14/2013 | 1/14/2013 8:57:31 AM | A | FAIL |
|
|
Installed a new 30 amp 240 volt 3 Phase circuit to a new twist-lock receptacle on ceiling. Please Final this when you are done. Thanks !!! Dan Phone #: ###-#### >> Inspection requested via web by Dan Mitchell NEC 400.5(A) Approval of equipment by third party testing laboratory tag NEC 400.5(A) under sized cord connected to equipment.
|
ELE13-00071
| Electrical Rough-In | 1/11/2013 | 1/14/2013 | 1/14/2013 8:11:08 AM | A | PASS |
|
|
Mike Phone #: ###-#### rough-in ok cover
|