Inspections for the day of: Wednesday, January 14, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00304 INSP-Sprinkler Rough-in1/14/20151/14/20151/16/2015 7:43:54 AMPPART
Verified added seismic brace at the first floor NE side, okayed for cover overhead work at the mail and print shop 1st floor- refer to dated annotations on plans. Need to provide new quick response heads per scope of permit work throughout the first floor- noted mixed standard and QR heads in the mail and print shop areas. Also completed rough-in inspection of the new dry system at the 2nd floor parking garage- items noted include; overspacing between two branchlines west end, missing coverage at the vestibule, provide flexible couplings at riser main between floors, missing forward flow provision at the riser, new outside WF bell needed.
FIR14-00182 INSP-Final Inspection1/14/20151/14/20151/15/2015 7:06:36 AMPPASS
Noted corrections and adjustments verified. Final inspection passed. Fire alarm permit finaled.
BLD14-01673 FIRE-Final Inspection1/14/20151/14/20151/14/2015 2:36:54 PMPPASS
Life safety passed after corrections made including signage at the main entry/exit, repaired exit/EM lights, tagged fire extinguishers. Blank deadbolt at the second exit and remove curtian at the back hall prior to structural final as agreed.
FIR14-00437 INSP-Sprinkler Rough-in/Hydro1/13/20151/14/20151/14/2015 2:33:25 PMPFAIL
24 hr air test failed due to an 8 psi loss at the guage-
BLD14-03143 FIRE-Final Inspection1/13/20151/14/20151/14/2015 2:14:36 PMPNR
Pending project related permit work. To be rescheduled per contractor.
BLD14-02720 FIRE-Final Inspection1/13/20151/14/20151/14/2015 11:29:02 AMAPASS
Fire life safety inspection completed acceptable. *Note- two new RTU's as shown on approved plans are not to be installed at this time per tenant.
BLD14-01673 FIRE-Final Inspection1/7/20151/14/20151/14/2015 10:58:14 AMANR
Pending current certification of fire extinguisher, discussed general requirements list on permit documents.
FIR14-00844 INSP-Final Inspection1/14/20151/14/20151/14/2015 10:53:22 AMPPASS
Fire sprinkler permit work approved for final. Noted items finished, walkthrough passed.
BLD14-03001 FIRE-Final Inspection1/13/20151/14/20151/14/2015 10:51:58 AMAPASS
Noted correction items verified for completion. Fire life safety inspection passed.
BLD14-03289 FIRE-Final Inspection1/13/20151/14/20151/14/2015 10:50:59 AMAPASS
Fire life safety inspection completed satisfactory. No modifications to the existing fire alarm or fire sprinkler systems were necessary due to remodel work.