FIR14-00304
| INSP-Sprinkler Rough-in | 1/14/2015 | 1/14/2015 | 1/16/2015 7:43:54 AM | P | PART |
|
|
Verified added seismic brace at the first floor NE side, okayed for cover overhead work at the mail and print shop 1st floor- refer to dated annotations on plans. Need to provide new quick response heads per scope of permit work throughout the first floor- noted mixed standard and QR heads in the mail and print shop areas. Also completed rough-in inspection of the new dry system at the 2nd floor parking garage- items noted include; overspacing between two branchlines west end, missing coverage at the vestibule, provide flexible couplings at riser main between floors, missing forward flow provision at the riser, new outside WF bell needed.
|
FIR14-00182
| INSP-Final Inspection | 1/14/2015 | 1/14/2015 | 1/15/2015 7:06:36 AM | P | PASS |
|
|
Noted corrections and adjustments verified. Final inspection passed. Fire alarm permit finaled.
|
BLD14-01673
| FIRE-Final Inspection | 1/14/2015 | 1/14/2015 | 1/14/2015 2:36:54 PM | P | PASS |
|
|
Life safety passed after corrections made including signage at the main entry/exit, repaired exit/EM lights, tagged fire extinguishers. Blank deadbolt at the second exit and remove curtian at the back hall prior to structural final as agreed.
|
FIR14-00437
| INSP-Sprinkler Rough-in/Hydro | 1/13/2015 | 1/14/2015 | 1/14/2015 2:33:25 PM | P | FAIL |
|
|
24 hr air test failed due to an 8 psi loss at the guage-
|
BLD14-03143
| FIRE-Final Inspection | 1/13/2015 | 1/14/2015 | 1/14/2015 2:14:36 PM | P | NR |
|
|
Pending project related permit work. To be rescheduled per contractor.
|
BLD14-02720
| FIRE-Final Inspection | 1/13/2015 | 1/14/2015 | 1/14/2015 11:29:02 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable. *Note- two new RTU's as shown on approved plans are not to be installed at this time per tenant.
|
BLD14-01673
| FIRE-Final Inspection | 1/7/2015 | 1/14/2015 | 1/14/2015 10:58:14 AM | A | NR |
|
|
Pending current certification of fire extinguisher, discussed general requirements list on permit documents.
|
FIR14-00844
| INSP-Final Inspection | 1/14/2015 | 1/14/2015 | 1/14/2015 10:53:22 AM | P | PASS |
|
|
Fire sprinkler permit work approved for final. Noted items finished, walkthrough passed.
|
BLD14-03001
| FIRE-Final Inspection | 1/13/2015 | 1/14/2015 | 1/14/2015 10:51:58 AM | A | PASS |
|
|
Noted correction items verified for completion. Fire life safety inspection passed.
|
BLD14-03289
| FIRE-Final Inspection | 1/13/2015 | 1/14/2015 | 1/14/2015 10:50:59 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory. No modifications to the existing fire alarm or fire sprinkler systems were necessary due to remodel work.
|