Inspections for the day of: Thursday, January 14, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00756 ELE-Aging Inspection1/14/20161/14/20161/14/2016 2:46:57 PM DONE
Still under construction
ELE13-00800 ELE-Aging Inspection1/14/20161/14/20161/14/2016 2:44:03 PM DONE
Still under construction
ELE16-00106 Permanent Service1/13/20161/14/20161/14/2016 2:43:13 PMPPASS
ALT # ###-#### - WE WILL BE IN THE TRAILER PARK ALL DAY. PLEASE CALL IF THERE IS AN ISSUE. THANK YOU Phone #: ###-#### Inspection requested via web by shane farwell
Outdoor receptacles not tamper or WR rated receptacles, contractor to inform general and take care of issue by final.
p/s u/g rec ok
ELE16-00108 Final1/13/20161/14/20161/14/2016 2:32:13 PMPPASS
ALT # ###-#### - WE WILL BE IN TRAILER PARK ALL DAY, CALL IF YOU HAVE AN ISSUE. THANK YOU Phone #: ###-#### Inspection requested via web by shane farwell
Service covered under permit ele15-01570. Underground ok and trailer final ok
ELE15-01570 Final1/14/20161/14/20161/14/2016 2:31:26 PMPPASS
Trailer hook up covered under permit #
ELE16-00108. Service Final ok
ELE16-00067 Electrical Rough-In1/14/20161/14/20161/14/2016 2:08:22 PMPPASS
Johathon Phone #: ###-#### Noticed loose ends near panel, box remove, secure. Bath area to remain unfinished til permitted. Wiring associated with items on permit rough in ok.
ELE15-02773 Final1/14/20161/14/20161/14/2016 1:07:39 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
110.3- Receptacles shall be connected as per instructions. GFCI below iron tripped but would not reset.
210.8(A)(2)- All 15 and 20 amp receptacle outlets located in garage shall have GFCI protection.
210.8(A)(6)- All receptacle outlets serving counter top in kitchen areas shall have GFCI protection. Butlers pantry.
210.52(C)- A receptacle outlet shall be located with in 24" of right side of counter in butlers pantry.
ELE15-03761 Final1/13/20161/14/20161/14/2016 11:26:33 AMAPASS
garage code is 1234 enter... Phone #: ###-#### Inspection requested via web by Richard Gratiot Final ok
ELE16-00114 Rough-In Permanent Service1/13/20161/14/20161/14/2016 10:45:16 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
210.52- Receptacle outlets shall be at ront and rear of dwelling. Front box cut in but not wired in.
ELE16-00113 Rough-In Permanent Service1/13/20161/14/20161/14/2016 10:12:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
rough in ok cover p/s u/g n ok
ELE16-00116 Final1/13/20161/14/20161/14/2016 9:03:32 AMACANC
Phone #: ###-#### Inspection requested via web by Kelly Felin
Kelly called asked to cancel and he would reschedule.