FIR15-00820
| INSP-Sprinkler Rough-in/Hydro | 1/14/2016 | 1/14/2016 | 1/14/2016 2:54:47 PM | P | PART |
|
|
2 hour hydrostatic test @ 200 psi passed/complete for dry system. 24 hour air test started at 1430hrs @ 45psi.
|
BLD15-04080
| FIRE-Final Inspection | 12/18/2015 | 1/14/2016 | 1/14/2016 11:33:56 AM | A | PASS |
|
|
Fire sprinkler testing/inspections for fire systems current, fire alarm testing/inspections current. Found a few exit signs that were INOP, tenant is aware and they have new exit signs on hand for replacement, work will be done by in house work crew. Life fire safety passed/complete.
|
BLD15-04197
| FIRE-Final Inspection | 1/13/2016 | 1/14/2016 | 1/14/2016 9:56:11 AM | A | PASS |
|
|
No fire alarm modifications, no fire sprinkler modifications, life fire safety inspection passed/complete.
|
BLD15-03695
| FIRE-Final Inspection | 1/13/2016 | 1/14/2016 | 1/14/2016 9:28:31 AM | A | PASS |
|
|
No fire sprinklers, no fire alarm modifications. Life fire safety inspection passed/complete
|