Inspections for the day of: Thursday, January 14, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00820 INSP-Sprinkler Rough-in/Hydro1/14/20161/14/20161/14/2016 2:54:47 PMPPART
2 hour hydrostatic test @ 200 psi passed/complete for dry system. 24 hour air test started at 1430hrs @ 45psi.
BLD15-04080 FIRE-Final Inspection12/18/20151/14/20161/14/2016 11:33:56 AMAPASS
Fire sprinkler testing/inspections for fire systems current, fire alarm testing/inspections current. Found a few exit signs that were INOP, tenant is aware and they have new exit signs on hand for replacement, work will be done by in house work crew. Life fire safety passed/complete.
BLD15-04197 FIRE-Final Inspection1/13/20161/14/20161/14/2016 9:56:11 AMAPASS
No fire alarm modifications, no fire sprinkler modifications, life fire safety inspection passed/complete.
BLD15-03695 FIRE-Final Inspection1/13/20161/14/20161/14/2016 9:28:31 AMAPASS
No fire sprinklers, no fire alarm modifications. Life fire safety inspection passed/complete