Inspections for the day of: Monday, January 14, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00136 Permanent Service1/10/20191/14/20191/14/2019 2:14:00 PMPPASS
Idaho Power is replacing transformer, they are shutting power off to the building about 8:30 AM we will be removing old gear and installing new service gear and equipment. Should be ready for inspection about 1:30 PM Phone #: ###-#### Inspection requested via web by Kurt Carlson
Main breaker panel board located in warehouse about 1/2 way down office wall towards east. New CT meter set on transformer on east side of building. Grounding electrode system, metal underground water pipe, ground rod and building steel. Unable to locate available fault current at time of inspection but verbally stated 10k below 50k rated main at 240 volt with 208 volt service. Will email AFC value to me as soon as located. p/s u/g rec ok
ELE19-00149 Electrical Rough-In1/14/20191/14/20191/14/2019 1:58:37 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender
Rough in ok cover
ELE19-00149 Permanent Service1/14/20191/14/20191/14/2019 1:41:34 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender
p/s u/g n ok
ELE19-00153 Temporary Service1/14/20191/14/20191/14/2019 1:00:08 PMPFAIL
Call Dean with questions Phone #: ###-#### Inspection requested via web by A.M.E. Office
590.6(B)- Temporary power receptacles other than 120 volt shall have GFCI protection. all 30 amp 2-pole twistlock receptacles
ELE19-00056 Final1/7/20191/14/20191/14/2019 11:00:32 AMAPASS
Please call when on the way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric
Owner provided garage door code. Final ok
ELE19-00056 Electrical Rough-In1/14/20191/14/20191/14/2019 10:13:48 AMPPASS
Please call when on the way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric
Wire fished in wall below panel. Rough in ok
ELE19-00127 Electrical Rough-In1/11/20191/14/20191/14/2019 10:12:50 AMAPASS
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Underground to pole bases rough in ok cover
ELE18-03493 Final1/11/20191/14/20191/14/2019 9:29:00 AMAPASS
Contact: Josh Mangum Phone #: ###-#### Inspection requested via web by Deb Gooden Only damaged feeders found supply Knitting Factory panels and have been locked out while others have been energized. Final ok
ELE18-01608 Electrical Rough-In1/11/20191/14/20191/14/2019 9:26:56 AMAPASS
Inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Underground south and east of EO Wilaon bldg rough in ok cover