ELE19-00136
| Permanent Service | 1/10/2019 | 1/14/2019 | 1/14/2019 2:14:00 PM | P | PASS |
|
|
Idaho Power is replacing transformer, they are shutting power off to the building about 8:30 AM we will be removing old gear and installing new service gear and equipment. Should be ready for inspection about 1:30 PM Phone #: ###-#### Inspection requested via web by Kurt Carlson Main breaker panel board located in warehouse about 1/2 way down office wall towards east. New CT meter set on transformer on east side of building. Grounding electrode system, metal underground water pipe, ground rod and building steel. Unable to locate available fault current at time of inspection but verbally stated 10k below 50k rated main at 240 volt with 208 volt service. Will email AFC value to me as soon as located. p/s u/g rec ok
|
ELE19-00149
| Electrical Rough-In | 1/14/2019 | 1/14/2019 | 1/14/2019 1:58:37 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Rough in ok cover
|
ELE19-00149
| Permanent Service | 1/14/2019 | 1/14/2019 | 1/14/2019 1:41:34 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender p/s u/g n ok
|
ELE19-00153
| Temporary Service | 1/14/2019 | 1/14/2019 | 1/14/2019 1:00:08 PM | P | FAIL |
|
|
Call Dean with questions Phone #: ###-#### Inspection requested via web by A.M.E. Office 590.6(B)- Temporary power receptacles other than 120 volt shall have GFCI protection. all 30 amp 2-pole twistlock receptacles
|
ELE19-00056
| Final | 1/7/2019 | 1/14/2019 | 1/14/2019 11:00:32 AM | A | PASS |
|
|
Please call when on the way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric Owner provided garage door code. Final ok
|
ELE19-00056
| Electrical Rough-In | 1/14/2019 | 1/14/2019 | 1/14/2019 10:13:48 AM | P | PASS |
|
|
Please call when on the way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric Wire fished in wall below panel. Rough in ok
|
ELE19-00127
| Electrical Rough-In | 1/11/2019 | 1/14/2019 | 1/14/2019 10:12:50 AM | A | PASS |
|
|
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground to pole bases rough in ok cover
|
ELE18-03493
| Final | 1/11/2019 | 1/14/2019 | 1/14/2019 9:29:00 AM | A | PASS |
|
|
Contact: Josh Mangum Phone #: ###-#### Inspection requested via web by Deb Gooden Only damaged feeders found supply Knitting Factory panels and have been locked out while others have been energized. Final ok
|
ELE18-01608
| Electrical Rough-In | 1/11/2019 | 1/14/2019 | 1/14/2019 9:26:56 AM | A | PASS |
|
|
Inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground south and east of EO Wilaon bldg rough in ok cover
|