ELE20-00028
| Permanent Service | 1/9/2020 | 1/14/2020 | 1/14/2020 2:08:52 PM | P | PASS |
|
|
There will be guys there working. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan p/s o/h rec ok
|
ELE20-00141
| Conference | 1/13/2020 | 1/14/2020 | 1/14/2020 1:54:44 PM | P | DONE |
|
|
Owner will be working at BSU and is requesting inspector to call number provided when inspector is on their way to residence. Phone #: ###-#### Inspection requested via web by Kelsey Timmons discussed protective stripps next to attic access, GFCI protection, tamper resistant receps.
|
ELE20-00148
| Electrical Rough-In | 1/14/2020 | 1/14/2020 | 1/14/2020 1:35:49 PM | P | PASS |
|
|
Please call Kengei at ###-#### a half an hour before inspection to insure access. He is the general contractor. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Master bath only ok to cover
|
ELE20-00135
| Temporary Service | 1/14/2020 | 1/14/2020 | 1/14/2020 1:35:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE19-04375
| Temporary Service | 1/14/2020 | 1/14/2020 | 1/14/2020 1:03:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE20-00134
| Temporary Service | 1/14/2020 | 1/14/2020 | 1/14/2020 1:02:51 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE19-04481
| Temporary Service | 1/14/2020 | 1/14/2020 | 1/14/2020 1:02:26 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE20-00098
| Rough-In Permanent Service | 1/13/2020 | 1/14/2020 | 1/14/2020 12:10:33 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Nermin Bobaric rough in ok p/s u/g n ok
|
ELE19-03040
| Final | 1/13/2020 | 1/14/2020 | 1/14/2020 11:20:52 AM | A | FAIL |
|
|
Please call drew with any questions @ ###-#### Phone #: ###-#### Inspection requested via web by William Salts 110.3 Kitchen gfci Lt of sink protects gfci rt of sink.(Double protected) 440.6 Mini split max fuse 15A, 40A installed. 210.52D Bath vanity shall have recep for each basin and on adjacent wall.
|
ELE19-01120
| Electrical Rough-In | 1/14/2020 | 1/14/2020 | 1/14/2020 11:10:46 AM | A | PASS |
|
|
basement bath floor heat Phone #: ###-#### Inspection requested via web by Jim Williams Floor heat only ok to cover
|
ELE19-00522
| Electrical Rough-In | 1/13/2020 | 1/14/2020 | 1/14/2020 10:03:38 AM | A | NR |
|
|
Evan Phone #: ###-#### needed conf.
|
ELE19-00522
| Conference | 1/14/2020 | 1/14/2020 | 1/14/2020 9:54:19 AM | A | PASS |
|
|
Evan Phone #: ###-#### Discussed Service change requirments. (Grounding and feeders must be installed before reconnect)
|
ELE20-00031
| Electrical Rough-In | 1/13/2020 | 1/14/2020 | 1/14/2020 9:38:28 AM | A | PASS |
|
|
Back door will be open. If you have any questions please feel free to contact Kaiden ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Clayton Morgan Corrections made Basement rough in only ok to cover
|
ELE19-00192
| Final | 1/7/2020 | 1/14/2020 | 1/14/2020 9:15:06 AM | A | PASS |
|
|
electrician not onsite. can call office for details. homeowner is blind, wife is blind and deaf. they have been notified you are coming this morning. Phone #: ###-#### Inspection requested via web by Matthew White Final ok
|
ELE19-04492
| Final | 1/13/2020 | 1/14/2020 | 1/14/2020 8:48:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt correction made final ok
|