Inspections for the day of: Tuesday, January 14, 2020.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00028 Permanent Service1/9/20201/14/20201/14/2020 2:08:52 PMPPASS
There will be guys there working. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan p/s o/h rec ok
ELE20-00141 Conference1/13/20201/14/20201/14/2020 1:54:44 PMPDONE
Owner will be working at BSU and is requesting inspector to call number provided when inspector is on their way to residence. Phone #: ###-#### Inspection requested via web by Kelsey Timmons discussed protective stripps next to attic access, GFCI protection, tamper resistant receps.
ELE20-00148 Electrical Rough-In1/14/20201/14/20201/14/2020 1:35:49 PMPPASS
Please call Kengei at ###-#### a half an hour before inspection to insure access. He is the general contractor. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Master bath only ok to cover
ELE20-00135 Temporary Service1/14/20201/14/20201/14/2020 1:35:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-04375 Temporary Service1/14/20201/14/20201/14/2020 1:03:12 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE20-00134 Temporary Service1/14/20201/14/20201/14/2020 1:02:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-04481 Temporary Service1/14/20201/14/20201/14/2020 1:02:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE20-00098 Rough-In Permanent Service1/13/20201/14/20201/14/2020 12:10:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Nermin Bobaric rough in ok p/s u/g n ok
ELE19-03040 Final1/13/20201/14/20201/14/2020 11:20:52 AMAFAIL
Please call drew with any questions @ ###-#### Phone #: ###-#### Inspection requested via web by William Salts 110.3 Kitchen gfci Lt of sink protects gfci rt of sink.(Double protected) 440.6 Mini split max fuse 15A, 40A installed. 210.52D Bath vanity shall have recep for each basin and on adjacent wall.
ELE19-01120 Electrical Rough-In1/14/20201/14/20201/14/2020 11:10:46 AMAPASS
basement bath floor heat Phone #: ###-#### Inspection requested via web by Jim Williams Floor heat only ok to cover
ELE19-00522 Electrical Rough-In1/13/20201/14/20201/14/2020 10:03:38 AMANR
Evan Phone #: ###-#### needed conf.
ELE19-00522 Conference1/14/20201/14/20201/14/2020 9:54:19 AMAPASS
Evan Phone #: ###-#### Discussed Service change requirments. (Grounding and feeders must be installed before reconnect)
ELE20-00031 Electrical Rough-In1/13/20201/14/20201/14/2020 9:38:28 AMAPASS
Back door will be open. If you have any questions please feel free to contact Kaiden ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Clayton Morgan Corrections made Basement rough in only ok to cover
ELE19-00192 Final1/7/20201/14/20201/14/2020 9:15:06 AMAPASS
electrician not onsite. can call office for details. homeowner is blind, wife is blind and deaf. they have been notified you are coming this morning. Phone #: ###-#### Inspection requested via web by Matthew White Final ok
ELE19-04492 Final1/13/20201/14/20201/14/2020 8:48:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt correction made final ok