Inspections for the day of: Tuesday, January 14, 2020.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00136 Final1/14/20201/14/20201/14/2020 4:12:06 PMPNR
Blake ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- A/C still needs electrical finished and locking caps installed
- condensate pump needs safety wired
- co sensors installed
- need to see an electrical permit issued
- re schedule inspection when work is finished
- co sensors needs installed by final
MEC20-00136 Pressure Test1/14/20201/14/20201/14/2020 4:09:04 PMPPASS
Please inspect in the PM. Call on way: Blake ###-####. Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- 5lb flue pressure test ok
- 20lb gas pressure test ok
- tagged meter location
MEC20-00118 Final1/14/20201/14/20201/14/2020 3:27:46 PMPFAIL
Unit #5 Inspection requested via web by Margie Rowe
- A/C needs locking caps installed on service ports
- pics of correction ok for final
MEC20-00130 Final1/10/20201/14/20201/14/2020 2:34:55 PMPPASS
field super: Jason Landers Phone #: ###-#### Inspection requested via web by Lisa Whitney
- furnace ac coil co ok
MEC20-00170 Final1/13/20201/14/20201/14/2020 1:52:30 PMPPASS
Please call Gener on your way and inspect later PM - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace only co ok
MEC19-05047 Final1/9/20201/14/20201/14/2020 1:36:33 PMPFAIL
Phone #: ###-#### Inspection requested via web by James Cox
- not an approved clearance reduction installed
- install b vent to achieve clearances
MEC20-00144 Final1/14/20201/14/20201/14/2020 1:20:00 PMPFAIL
Inspection requested via web by Margie Rowe
- A/C needs service clearances per manufactures specs
MEC19-04664 Final1/9/20201/14/20201/14/2020 10:57:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- range vent needs installed and vented
- need fireplace installation instructions onsite
- A/C needs locking caps installed on service ports
MEC20-00172 Final1/13/20201/14/20201/14/2020 10:39:04 AMAPASS
Please call Mary prior to arrival if possible. ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- furnace only co ok
MEC19-05744 Final1/9/20201/14/20201/14/2020 9:46:35 AMAPASS
Please call Robert in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout
- furnace ac coil co ok
MEC19-05712 Final1/13/20201/14/20201/14/2020 9:20:23 AMAPASS
call ###-#### anytime after 9am
- final ok
MEC20-00144 Final1/13/20201/14/20201/14/2020 9:20:08 AMANH
Inspection requested via web by Margie Rowe
- no access to home left notice on front door
MEC20-00150 Pressure Test1/13/20201/14/20201/14/2020 8:57:22 AMAPASS
Pressure test and gas insert inspection. Please call Jason prior to arrival. Would like inspection as early as possible. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft
- 20lb gas pressure test ok
MEC20-00150 Rough-in1/14/20201/14/20201/14/2020 8:57:05 AMAFAIL
Pressure test and gas insert inspection. Please call Jason prior to arrival. Would like inspection as early as possible. Phone #: ###-#### Inspection requested via web by Jamee
Shoecraft
- CSST needs sleeved through masonary chimney
- sags in gas line need more support
- fireplace insert R/I ok
MEC19-02752 Mec-Aging Inspection1/14/20201/14/20201/14/2020 8:05:00 AM FAIL
Permit has not been active since 6-25-19. Schedule inspection with owner if work is finished. Permit will expired at next mechanical aging inspection if not active