ELE97-02474
| INSP - T/S and Final | 1/14/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | A | CANC |
|
|
01/14/98 403 - Scheduled by Hello!. Contact phone is [3857310]. WRONG PERMIT NUMBER CALLED, WILL RESCHEDULE.
|
ELE97-03775
| INSP - Electrical Rough-In | 1/14/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | A | NR |
|
|
01/14/98 403 - p\s ###-#### CONTRACTOR WILL RESCHEDULE.
|
ELE98-00087
| INSP - Final | 1/13/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | A | PASS |
|
|
01/14/98 403 - ZAPPA JUICE--FLOURESCENT LIGHTING
|
ELE98-00105
| INSP - Electrical Rough-In | 1/14/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | A | PASS |
|
|
01/14/98 403 - P\s ###-####
|
ELE97-00430
| INSP - Conference | 1/15/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | P | PASS |
|
|
DISCUSSED AREAS NEEDED FOR FINALING.
|
ELE98-00089
| INSP - Electrical Rough-In | 1/15/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | P | FAIL |
|
|
01/15/98 403 - THIS IS FOR THE SERVICE.. NEC: 250-81(A). SHALL HAVE SERVICE EQUIPTMENT GROUNDED TO WATER PIPE SYSTEM. NEC: 250-71(A). SERVICE EQUIPTMENT SHALL BE BONDED TOGETHER. NEC: 250- TWO OR MORE BUILDINGS, A GROUNDING ELECTRODE. NEC: 373-4. OPENINGS CLOSED IN CABINETS, ETC.
|
ELE97-04461
| INSP - Final | 1/14/1998 | 1/15/1998 | 1/15/1998 12:00:00 AM | P | PASS |
|
|
01/15/98 403 - COMPUTER OUTLETS--JESSICA WILL CALL YOU AT 1:15 ABOUT THE ISOLATED GROUNDING CIRCUITS FOR COMPUTERS IN CLASSROOMS.
|