Inspections for the day of: Thursday, January 15, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00353 FIR-Aging Inspection1/15/20041/15/20041/15/2004 12:00:00 AM PASS
this project is still under construction 1/15/2004 9:42:15 AM
FIR03-00765 INSP-Final Inspection1/15/20041/15/20041/15/2004 12:00:00 AMAPASS
The FACP has 8 zones and is full; the BFP tamper switches are not on a separate zone; the BFP has the wall PIV tamper on one side an OS and Y tamper on the other 1/15/2004 9:19:30 AM
BLD03-02635 FIRE-Conference1/15/20041/15/20041/15/2004 12:00:00 AMAPART
met with GC while testing the fire alarm; will need emergency lighting; occupant load sign and address for final; requested data for Auto-Fry to clarify if it is capable of providing a contact for connection to fire alarm upon activation of self contained extinguishing system 1/15/2004 9:24:17 AM
FIR03-00749 INSP-Final Inspection1/14/20041/15/20041/15/2004 12:00:00 AMAPASS
jon; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD03-02828 FIRE-Final Inspection1/15/20041/15/20041/15/2004 12:00:00 AMPPASS
chris; Phone #: ###-#### Internet Inspection Request from: Darla Downs Will have ADA compliant hardware on restroom for strcutural inspector 1/15/2004 3:25:16 PM
FIR03-00749 INSP-Final Inspection1/13/20041/15/20041/15/2004 12:00:00 AMPPASS
adam; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR03-00560 INSP-Final Inspection1/13/20041/15/20041/15/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 1/13/2004 at 1:55:05 PM. Contact: ###-####.