ELE08-00123
| Electrical Rough-In | 1/15/2008 | 1/15/2008 | 1/15/2008 3:10:28 PM | P | PASS |
|
|
wes Phone #: ###-#### - the later the better - please call 1/2 hr prior to inspection ok
|
ELE07-03440
| Electrical Rough-In | 1/15/2008 | 1/15/2008 | 1/15/2008 2:21:21 PM | P | PART |
|
|
Inspect to cover trench for service feeder conuits. Phone #: ###-#### Internet Inspection Request from: Alan Lusk feeders to sub panels and loading dock u/g ok
|
ELE08-00106
| Electrical Rough-In | 1/15/2008 | 1/15/2008 | 1/15/2008 1:29:10 PM | P | FAIL |
|
|
daniel Phone #: ###-#### corr called 110.3(A) laundry outlet romex damaged, 230.2 olny one p/s allowed for duplex, T250.122 needs #12 equip grd pigtail for disposal switch east side, 314.17(A)&C) replace all 2,3,4 gang boxes with broken out internal clamps
|
ELE08-00119
| Rough-In Permanent Service | 1/14/2008 | 1/15/2008 | 1/15/2008 9:53:09 AM | A | PASS |
|
|
Shawn ###-#### r/i p/s u/g new ok called needs to protect cables by attic access
|
ELE07-01624
| Final | 1/15/2008 | 1/15/2008 | 1/15/2008 9:07:47 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 1/15/2008 at 7:30:30 AM. Contact: ###-####. helped 370 with final
|