Inspections for the day of: Tuesday, January 15, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00637 INSP-Final Inspection1/14/20081/15/20081/15/2008 6:00:23 PMPFAIL
Forward flush passed. To final the project the 1 1/4" branchline needs to be relocated around the electrical room.
FIR08-00026 INSP-Sprinkler Rough-in1/15/20081/15/20081/15/2008 4:37:04 PMPPASS
The 5' stub out is ok to cover.
FIR07-00686 INSP-Alarm Testing1/14/20081/15/20081/15/2008 4:36:13 PMADONE
See the city approved plans for items tested and deficiencies noted.
FIR07-01024 INSP-Sprinkler Rough-in1/14/20081/15/20081/15/2008 2:26:24 PMAPASS
Sprinkler piping is ok to cover.
BLD08-00046 FIRE-Final Inspection1/11/20081/15/20081/15/2008 2:25:31 PMAFAIL
Tag the fire extinguishers, provide hardware on the required exit doors, cover the "exit" text on the doors that are not going to be used for exits and repair the trouble signals on the fire alarm panel. Also repair the fire dept access signs at the property entrances.
BLD07-02601 FIRE-Final Inspection1/14/20081/15/20081/15/2008 2:23:24 PMAFAIL
Repair the main exit doors, remove the u hooks from the rear door and provide the occupant load sign for 105 people.