Inspections for the day of: Thursday, January 15, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00626 INSP-Sprinkler Rough-in/Hydro1/15/20091/15/20091/15/2009 4:38:07 PMPPASS
See the city approved plans for the Storage area that the sprinkler piping is ok to cover.
BLD09-00004 FIRE-Final Inspection1/14/20091/15/20091/15/2009 4:37:02 PMPFAIL
Provide the city approved drawings for the inspection. Provide atleast one 2A10BC fire extinguisher in a normal path of travel with a current inspection tag. Remove the padlock hasp from the west exit door. Provide lever hardware on the west exit door. Provide lever hardware on the south exit door. Remove the thumbturn deadbolts from the east exit door. A keyed lock is allowed on the east exit door as discussed with the sticker "Door to remain unlocked while building is occupied".
FIR08-00772 INSP-Sprinkler Rough-in1/14/20091/15/20091/15/2009 3:42:40 PMPFAIL
Remove 1" valve or provide tamper switch on the valve controlling water to the elevator shaft. The upright sprinklers along column line "D" are overspaced by being 8'-0" off of the column line/roof deck transition. The tamper switch on the backflow preventor does not meet the requirements of NFPA 72. Several sprinkler pendants on the second floor are located too close to the supply registers. Standard responce upright heads have been mixed with new quick responce heads over the sales floor. Earthquake bracing is missing on the 4" main. An additional pendant head is needed in the first floor storage room. Provide sprinkler coverage under the landing at the west stairs.
BLD09-00025 FIRE-Final Inspection1/14/20091/15/20091/15/2009 2:31:13 PMPFAIL
Provide correct floor plan and provide approved single action hardware on one of the east facing exit doors.
BLD09-00024 FIRE-Final Inspection1/14/20091/15/20091/15/2009 2:30:52 PMPFAIL
Provide correct floor plan and provide approved single action hardware on one of the east facing exit doors.
BLD08-02270 FIRE-Final Inspection1/15/20091/15/20091/15/2009 12:22:12 PMPPASS
life safety passed
FIR08-00854 INSP-Final Inspection1/15/20091/15/20091/15/2009 12:21:12 PMPPASS
permit finaled
FIR08-00854 INSP-Alarm Testing1/14/20091/15/20091/15/2009 12:13:31 PMAPASS
Permit finaled
FIR09-00021 INSP-Sprinkler Rough-in1/14/20091/15/20091/15/2009 8:52:14 AMAPASS
Permit passed. Any questions contact Scott Arlenno in Fire.