FIR12-00557
| INSP-Final Inspection | 1/15/2013 | 1/15/2013 | 1/16/2013 9:22:08 AM | P | CANC |
|
|
To be canceled per Rand Phone #: ###-####
|
FIR12-00583
| INSP-Sprinkler Rough-in | 1/15/2013 | 1/15/2013 | 1/15/2013 3:06:47 PM | P | PASS |
|
|
Tenting passed. Sprinkler piping can be covered.
|
FIR12-00661
| INSP-Sprinkler Rough-in | 1/14/2013 | 1/15/2013 | 1/15/2013 3:06:16 PM | P | PASS |
|
|
The tenting inspection passed. Sprinkler piping is ok to cover.
|
BLD12-01909
| FIRE-Conference | 1/15/2013 | 1/15/2013 | 1/15/2013 3:04:54 PM | P | DONE |
|
|
Sprinkler piping is ok to cover. Tag on window
|
BLD12-03046
| FIRE-Final Inspection | 1/14/2013 | 1/15/2013 | 1/15/2013 11:04:33 AM | A | PART |
|
|
A temporary occupancy was given with Scott Arellano's permission until the fire alarm aspect of the project has been addressed. A permit needs to be pulled to tie in one duct smoke detector to the existing fire alarm system. The second duct smoke detector either needs to be connected as well or removed since it appears to meet the exception of the mechanical code for supplying air within a single compartment.
|