Inspections for the day of: Wednesday, January 15, 2014.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01260 ELE-Aging Inspection1/15/20141/15/20141/17/2014 4:07:29 PM DONE
Waiting on owner
ELE13-01291 Final1/15/20141/15/20141/15/2014 4:37:58 PMPPASS
lea electric Phone #: ###-#### 5th floor "jump" floor pour rough in ok cover
ELE13-02833 Electrical Rough-In1/15/20141/15/20141/15/2014 4:00:12 PMPFAIL
>> Inspection requested via web by Rhonda Zamagni 300.4- NM cable shall be protected where ran through bored hole that is less than 1 1/4" from framing surface.
300.4- Raceways containing conductors larger than #4 shall have bushing where they enter box.
250.32(A)- A seperate structure supplied by feeders or branch circuits shall have a grounding electrode system installed.
250.32(B)- For a grounded system at the seperate structure an equptment grounding conductor as described in 250.118 shall be run with the supply conductors and be connected at disconnecting means and grounding electrode. Increase room count on permit to 14 rooms. No number provided to contact contractor. Ok to foam seal
ELE14-00063 Final1/13/20141/15/20141/15/2014 3:30:19 PMPNR
We upgraded the electrical service from 100 amps to 200 amps. Please try to make this the last inspection of your day, if possible.
Thanks !!! Dan cell ####-#### Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Labelling not complete
ELE14-00063 Rough-In Permanent Service1/13/20141/15/20141/15/2014 3:29:33 PMPPASS
We upgraded the electrical service from 100 amps to 200 amps. Please try to make this the last inspection of your day, if possible.
Thanks !!! Dan cell ####-#### Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Informed contractor to reduce height of mast for safe reconnect. Service change rough in ok. p/s o/h rec ok
ELE14-00112 Electrical Rough-In1/15/20141/15/20141/15/2014 3:04:02 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Kendra Lanham Rough in ok cover
ELE14-00100 Permanent Service1/15/20141/15/20141/15/2014 2:02:54 PMPPASS
Jack Phone #: ###-#### p/s o/h rec ok
ELE13-03539 Electrical Rough-In1/15/20141/15/20141/15/2014 1:49:19 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt Wall rough in ok cover
ELE14-00115 Electrical Rough-In1/15/20141/15/20141/15/2014 1:36:39 PMPPASS
Exterior underground work at rear of building. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Under ground service entrance conduit rough in ok cover
GCE13-00168 GCE-Rough-In1/15/20141/15/20141/15/2014 12:14:41 PMPPASS
Barbara ###-#### Ceiling rough in ok cover
GCE13-00207 GCE-Final1/15/20141/15/20141/15/2014 10:55:43 AMPPART
Parking lot light poles not finished. Building ok
ELE14-00099 Final1/14/20141/15/20141/15/2014 10:19:37 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Temp service final ok
ELE14-00099 Temporary Service1/15/20141/15/20141/15/2014 10:05:00 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman
t/s o/h n ok
ELE13-01921 Final1/14/20141/15/20141/15/2014 10:02:57 AMACANC
roger Phone #: ###-#### Requested a different job for inspection
ELE13-03498 Electrical Rough-In1/14/20141/15/20141/15/2014 9:45:04 AMAPASS
Lockbox code is 3811. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Back building rough in ok cover
ELE13-03338 Electrical Rough-In1/14/20141/15/20141/15/2014 9:26:34 AMAPASS
need floor heat inspection. Please call about an hour before inspection time so I can insure someone will be there. Thanks. Phone #: ###-#### >> Inspection requested via web by Jerry Moore Master bath floor heat rough in ok cover
ELE13-03004 Final1/14/20141/15/20141/15/2014 9:00:01 AMAPASS
call for access // Charlie Phone #: ###-#### Final ok
ELE13-03312 Final1/15/20141/15/20141/15/2014 8:05:20 AMPPASS
Final ok
ELE14-00078 Permanent Service1/14/20141/15/20141/14/2014 2:59:54 PMAPASS
kevin Phone #: ###-#### p/s o/h rec ok