ELE10-01260
| ELE-Aging Inspection | 1/15/2014 | 1/15/2014 | 1/17/2014 4:07:29 PM | | DONE |
|
|
Waiting on owner
|
ELE13-01291
| Final | 1/15/2014 | 1/15/2014 | 1/15/2014 4:37:58 PM | P | PASS |
|
|
lea electric Phone #: ###-#### 5th floor "jump" floor pour rough in ok cover
|
ELE13-02833
| Electrical Rough-In | 1/15/2014 | 1/15/2014 | 1/15/2014 4:00:12 PM | P | FAIL |
|
|
>> Inspection requested via web by Rhonda Zamagni 300.4- NM cable shall be protected where ran through bored hole that is less than 1 1/4" from framing surface. 300.4- Raceways containing conductors larger than #4 shall have bushing where they enter box. 250.32(A)- A seperate structure supplied by feeders or branch circuits shall have a grounding electrode system installed. 250.32(B)- For a grounded system at the seperate structure an equptment grounding conductor as described in 250.118 shall be run with the supply conductors and be connected at disconnecting means and grounding electrode. Increase room count on permit to 14 rooms. No number provided to contact contractor. Ok to foam seal
|
ELE14-00063
| Final | 1/13/2014 | 1/15/2014 | 1/15/2014 3:30:19 PM | P | NR |
|
|
We upgraded the electrical service from 100 amps to 200 amps. Please try to make this the last inspection of your day, if possible. Thanks !!! Dan cell ####-#### Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Labelling not complete
|
ELE14-00063
| Rough-In Permanent Service | 1/13/2014 | 1/15/2014 | 1/15/2014 3:29:33 PM | P | PASS |
|
|
We upgraded the electrical service from 100 amps to 200 amps. Please try to make this the last inspection of your day, if possible. Thanks !!! Dan cell ####-#### Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Informed contractor to reduce height of mast for safe reconnect. Service change rough in ok. p/s o/h rec ok
|
ELE14-00112
| Electrical Rough-In | 1/15/2014 | 1/15/2014 | 1/15/2014 3:04:02 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Kendra Lanham Rough in ok cover
|
ELE14-00100
| Permanent Service | 1/15/2014 | 1/15/2014 | 1/15/2014 2:02:54 PM | P | PASS |
|
|
Jack Phone #: ###-#### p/s o/h rec ok
|
ELE13-03539
| Electrical Rough-In | 1/15/2014 | 1/15/2014 | 1/15/2014 1:49:19 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Wall rough in ok cover
|
ELE14-00115
| Electrical Rough-In | 1/15/2014 | 1/15/2014 | 1/15/2014 1:36:39 PM | P | PASS |
|
|
Exterior underground work at rear of building. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Under ground service entrance conduit rough in ok cover
|
GCE13-00168
| GCE-Rough-In | 1/15/2014 | 1/15/2014 | 1/15/2014 12:14:41 PM | P | PASS |
|
|
Barbara ###-#### Ceiling rough in ok cover
|
GCE13-00207
| GCE-Final | 1/15/2014 | 1/15/2014 | 1/15/2014 10:55:43 AM | P | PART |
|
|
Parking lot light poles not finished. Building ok
|
ELE14-00099
| Final | 1/14/2014 | 1/15/2014 | 1/15/2014 10:19:37 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Temp service final ok
|
ELE14-00099
| Temporary Service | 1/15/2014 | 1/15/2014 | 1/15/2014 10:05:00 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman t/s o/h n ok
|
ELE13-01921
| Final | 1/14/2014 | 1/15/2014 | 1/15/2014 10:02:57 AM | A | CANC |
|
|
roger Phone #: ###-#### Requested a different job for inspection
|
ELE13-03498
| Electrical Rough-In | 1/14/2014 | 1/15/2014 | 1/15/2014 9:45:04 AM | A | PASS |
|
|
Lockbox code is 3811. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Back building rough in ok cover
|
ELE13-03338
| Electrical Rough-In | 1/14/2014 | 1/15/2014 | 1/15/2014 9:26:34 AM | A | PASS |
|
|
need floor heat inspection. Please call about an hour before inspection time so I can insure someone will be there. Thanks. Phone #: ###-#### >> Inspection requested via web by Jerry Moore Master bath floor heat rough in ok cover
|
ELE13-03004
| Final | 1/14/2014 | 1/15/2014 | 1/15/2014 9:00:01 AM | A | PASS |
|
|
call for access // Charlie Phone #: ###-#### Final ok
|
ELE13-03312
| Final | 1/15/2014 | 1/15/2014 | 1/15/2014 8:05:20 AM | P | PASS |
|
|
Final ok
|
ELE14-00078
| Permanent Service | 1/14/2014 | 1/15/2014 | 1/14/2014 2:59:54 PM | A | PASS |
|
|
kevin Phone #: ###-#### p/s o/h rec ok
|