Inspections for the day of: Wednesday, January 15, 2014.
Number of inspections: 6
Percentage of inspections complete: 83 %
Percentage of inspections not complete: 17 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00721 INSP-Sprinkler Rough-in1/14/20141/15/20141/15/2014 3:34:28 PMPPART
Three locations as marked on the plans need pendant head modifications. Wood above the ceiling needs to be removed as per conversation with Jason with HC Company. Piping can be covered and items will be checked at the final inspection.
FIR13-00612 INSP-Sprinkler Rough-in1/14/20141/15/20141/15/2014 2:00:11 PMAFAIL
Piping as installed is ok except for an overspaced pendant and a blocked pendant. Plans need to be resubmitted due to extensive pipe re-routing and additional fittings in the supply piping which will effect the hydraulic calculations. No tenting has been performed/installed yet. No cover of piping is allowed yet.
BLD13-02237 FIRE-Conference1/14/20141/15/20141/15/2014 1:58:21 PMADONE
I went over life safety requirements with Marcus, the owner. One additional exit discharge light is needed at the northwest exit door, additional fire extinguishers for the seating area and a K class for the kitchen. It appears that a sprinkler monitoring system is required but its existance on site could not be verified, Marcus is going to follow up. The new kitchen hood suppression system will need to be connected to this fire alarm system as well as a separate permit for the work. The fire sprinkler permit still needs to be finaled and the fire suppression permit needs to be tested and finaled. All other items appear to be ok.
BLD13-02152 FIRE-Final Inspection1/14/20141/15/20141/15/2014 1:54:23 PMAFAIL
Provide exit sign over door marked on the approved plans and provide emergency lighting as per approved plans. Also provide annual inspection for the fire extinguishers.
FIR13-00612 INSP-Sprinkler Rough-in/Hydro1/14/20141/15/20141/14/2014 2:30:22 PMACANC
Please call 45 min prior to inspection. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD08-00870 FIRE-Conference1/15/20141/15/2014 P 
Could you check this out and see if it is resolved so we can close permit?