BLD15-01943
| FIRE-Final Inspection | 1/15/2016 | 1/15/2016 | 1/15/2016 2:28:17 PM | P | PASS |
|
|
life safety passed
|
FIR15-00608
| INSP-Final Inspection | 1/15/2016 | 1/15/2016 | 1/15/2016 2:02:27 PM | P | PASS |
|
|
Permit finaled. Smoke detector has been added and addresses match the approved plans.
|
BLD16-00117
| FIRE-Final Inspection | 1/15/2016 | 1/15/2016 | 1/15/2016 1:42:17 PM | P | PASS |
|
|
life safety passed. Two fryers have been removed until a permit is issued for the new piping arrangement that will be requirred for the hood suppression system.
|
BLD15-00247
| FIRE-Final Inspection | 1/14/2016 | 1/15/2016 | 1/15/2016 12:50:17 PM | A | PASS |
|
|
Life safety passed
|
BLD14-01680
| FIRE-Final Inspection | 1/14/2016 | 1/15/2016 | 1/15/2016 12:18:59 PM | A | PASS |
|
|
Life safety passed
|
FIR14-00518
| INSP-Final Inspection | 1/14/2016 | 1/15/2016 | 1/15/2016 12:18:05 PM | A | PASS |
|
|
Permit finaled
|
FIR15-00660
| INSP-Final Inspection | 1/14/2016 | 1/15/2016 | 1/15/2016 11:33:00 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00870
| INSP-Final Inspection | 1/14/2016 | 1/15/2016 | 1/15/2016 9:50:50 AM | A | PASS |
|
|
Permit finaled
|
BLD16-00117
| FIRE-Final Inspection | 1/14/2016 | 1/15/2016 | 1/15/2016 9:05:01 AM | A | FAIL |
|
|
Provide recertification for the fire extinguishers and hood suppression system. The hood suppression system may require permits for work to be performed. Repair or remove the non functional emergency light
|
FIR15-00715
| INSP-Sprinkler Rough-in | 1/14/2016 | 1/15/2016 | 1/15/2016 9:00:11 AM | A | FAIL |
|
|
Tenting has not been corrected. Do not cover piping.
|
FIR15-00717
| INSP-Sprinkler Rough-in | 1/14/2016 | 1/15/2016 | 1/15/2016 8:58:49 AM | A | FAIL |
|
|
Tenting has not been corrected. Do not cover piping.
|
FIR15-00608
| INSP-Final Inspection | 1/12/2016 | 1/15/2016 | 1/15/2016 8:22:14 AM | A | FAIL |
|
|
A smoke detector shown as existing is actually missing. Will need to be added to match plans and to meet spacing requirements.
|