MEC18-04929
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 4:07:16 PM | P | PASS |
|
|
LOCKBOX 1976 Inspection requested via web by Aaron Alandt - final ok
|
MEC19-00149
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 3:00:30 PM | P | FAIL |
|
|
If possible set inspection for around 3 pm. We will need to perform pressure test while inspector is present. Please call Josh at ###-#### Thank you Phone #: ###-#### Inspection requested via web by Andrea Grigsby - 5lb flue test fail
|
MEC19-00176
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 2:13:10 PM | P | NH |
|
|
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - no access to home left notice on front door
|
MEC18-05695
| Rough-in | 1/15/2019 | 1/15/2019 | 1/15/2019 2:12:28 PM | P | FAIL |
|
|
12 units on south side of bld c
- units on each floor need duct seal and flex installed per manufacturers specs - this inspection was called in this afternoon under the wrong mech permit which was building A
|
MEC19-00130
| Rough-in | 1/15/2019 | 1/15/2019 | 1/15/2019 1:38:27 PM | P | FAIL |
|
|
12 units // Oleg Phone #: ###-#### - scheduled wrong permit should have been bld c
|
MEC19-00205
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 1:23:54 PM | P | NR |
|
|
Early PM please call Dan prior to arrival ###-#### Inspection requested via web by Arielle Hendricks
|
MEC18-06034
| DOC - Permit Finaled | 1/15/2019 | 1/15/2019 | 1/15/2019 1:14:44 PM | P | PASS |
|
|
final ok
|
MEC18-06034
| Pressure Test | 1/11/2019 | 1/15/2019 | 1/15/2019 1:14:20 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Field - 20lb gas pressure test for range ok
|
MEC19-00023
| Pressure Test | 1/15/2019 | 1/15/2019 | 1/15/2019 11:01:55 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Field - 60 lb gas pressure test ok - tagged meter bar
|
MEC19-00215
| Pressure Test | 1/14/2019 | 1/15/2019 | 1/15/2019 11:01:11 AM | A | PASS |
|
|
gage at range location Inspection requested via web by anthony allen - 20lb gas pressure test pass for range - make sure to seal penetration outside and penetration through floor
|
MEC19-00201
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 10:34:46 AM | A | FAIL |
|
|
If no answer welcome to check shop in backyard.. no dogs on property // Phil Phone #: ###-#### - line set needs UV protection -gas line at furnace needs a sediment trap after shut off -A/C max amps is 20 breaker at panel is a 30 amp - electrical permit needs pulled for new A/C installed
|
MEC18-01349
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 9:51:40 AM | A | NH |
|
|
Please call ahead 20 minutes // Brie Phone #: ###-#### - no access to home left notice on front door - reschedule with owner
|
MEC18-05264
| Final | 1/14/2019 | 1/15/2019 | 1/15/2019 9:27:36 AM | A | FAIL |
|
|
garage code 6074 Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- protection barriers in front of water heater and furnace are not secured down to concrete
|
MEC19-00122
| Pressure Test | 1/14/2019 | 1/15/2019 | 1/15/2019 8:56:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - gauge wont zero stuck at 17lb
|
MEC19-00122
| Rough-in | 1/14/2019 | 1/15/2019 | 1/15/2019 8:55:44 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - no access to attic need to check furnace
|
MEC19-00149
| Final | 1/14/2019 | 1/15/2019 | 1/14/2019 11:31:03 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Andrea Grigsby Inspection cancelled from web by: Andrea Grigsby
|