FIR19-00559
| INSP-Final Inspection | 1/13/2020 | 1/15/2020 | 1/15/2020 4:08:30 PM | P | PART |
|
|
Inspection performed by Lee Meridith, reference notes entered under Jim Page name on the 15JAN2019 for remaining items that need to be tested as well as correction items.
We are ready for a gander -Neal T. ###-#### Phone #: ###-#### Inspection requested via web by Neal Timmerman
|
BLD19-00658
| FIRE-Conference | 1/15/2020 | 1/15/2020 | 1/15/2020 3:53:02 PM | P | DONE |
|
|
Follow up conference scheduled for 16JAN2020 for question asked about attic sprinkler coverage, need further verification for sprinkler head coverage in question.
Josh Phone #: ###-####
|
BLD19-04756
| FIRE-Final Inspection | 1/15/2020 | 1/15/2020 | 1/15/2020 3:50:39 PM | P | CANC |
|
|
Alice Phone #: ###-####
|
FIR19-00940
| INSP-Sprinkler Rough-in | 1/14/2020 | 1/15/2020 | 1/15/2020 3:50:27 PM | P | PASS |
|
|
Rough to cover inspection for underground supply and remote FDC complete, approved for cover.
Underground rough to cover. Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-04765
| FIRE-Final Inspection | 1/15/2020 | 1/15/2020 | 1/15/2020 3:46:56 PM | P | PASS |
|
|
Previously noted items by Mike Jordan have been corrected, no fire sprinklers, no fire alarms, fire exitnguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.
|
FIR18-00858
| INSP-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 2:32:55 PM | P | PART |
|
|
No noted items for level 1 walkthrough.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR18-00840
| INSP-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 2:31:47 PM | P | FAIL |
|
|
Items requiring correction have been notated on city approved draiwngs. Level 1 has an A/V device missing, candella setings that do not match the plans and a couple of A/V's that are overspaced.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR19-00906
| INSP-Sprinkler Rough-in | 1/14/2020 | 1/15/2020 | 1/15/2020 11:03:18 AM | A | CANC |
|
|
Piping was covered in snow and concrete blanket, piping/fitting could not be seen in the trench, inspection will need to be rescheduled when pipe is visible, this request is cancelled.
Underground rough to cover. Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-03936
| FIRE-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 11:01:55 AM | A | FAIL |
|
|
2 areas have fire sprinklers that are less than 6 feet apart, fire sprinkler modifications are required for area of work to be compliant with NFPA13. Any and all fire sprinkler modifications requires a seperate permit.
are will be onsite after 9am. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
|
BLD19-04374
| FIRE-Final Inspection | 1/15/2020 | 1/15/2020 | 1/15/2020 10:21:20 AM | A | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
|
FIR20-00025
| INSP-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 9:38:20 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Inspecting technician: Ray McQueen, building has open access Phone #: ###-#### Inspection requested via web by Rose Peterson
|
BLD18-01083
| FIRE-Conference | 1/14/2020 | 1/15/2020 | 1/15/2020 9:16:12 AM | A | CANC |
|
|
Conference anceled per voicemail from point of contact, will be rescheduled for a later date.
call prior mike Phone #: ###-####
|
BLD19-03650
| FIRE-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 9:15:24 AM | A | CANC |
|
|
Fire alarm permit is still in issued status, needs finaled before life fire safety can be completed, this request is cancelled.
Zach Phone #: ###-####
|
BLD19-00416
| FIRE-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 9:12:18 AM | A | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for area of work complete.
Bruce Phone #: ###-####
|
BLD19-04945
| FIRE-Final Inspection | 1/14/2020 | 1/15/2020 | 1/14/2020 9:53:37 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
Tim Phone #: ###-####
|