BLD03-01474
| FIRE-Final Inspection | 1/14/2004 | 1/16/2004 | 1/16/2004 12:00:00 AM | A | FAIL |
|
|
BILL; Phone #: ###-#### Internet Inspection Request from: Darla Downs need to complete alarm permit; gaurdrail at mezzanine not installed 1/16/2004 11:05:46 AM
|
BLD03-02848
| FIRE-Final Inspection | 1/16/2004 | 1/16/2004 | 1/16/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/16/2004 at 7:20:15 AM. Contact: ###-####. doors with mag hold opens require smoke detectors for door release; penetrations in three hour wall require firestopping; exit sign needed as shown on plans; door to east stair to have passage set; fire sprinklers within 6 ft of each other by west exit; smoke detector required above FACP 1/16/2004 3:01:51 PM
|
FIR03-00698
| INSP-Final Inspection | 1/16/2004 | 1/16/2004 | 1/16/2004 12:00:00 AM | A | FAIL |
|
|
duct detector not shutting AHU off; had to adjust strobes to proper CD in several areas; need updated map and record of completion 1/16/2004 11:05:19 AM
|
FIR03-00759
| INSP-Sprinkler Rough-in | 1/16/2004 | 1/16/2004 | 1/16/2004 12:00:00 AM | P | FAIL |
|
|
installed per plans however there are two heads located within 6 ft of each other - located by west exit doors 1/16/2004 2:39:57 PM
|
FIR03-00302
| INSP-Final Inspection | 1/16/2004 | 1/16/2004 | 1/16/2004 12:00:00 AM | P | PASS |
|
|
|