Inspections for the day of: Friday, January 16, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01474 FIRE-Final Inspection1/14/20041/16/20041/16/2004 12:00:00 AMAFAIL
BILL; Phone #: ###-#### Internet Inspection Request from: Darla Downs need to complete alarm permit; gaurdrail at mezzanine not installed 1/16/2004 11:05:46 AM
BLD03-02848 FIRE-Final Inspection1/16/20041/16/20041/16/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 1/16/2004 at 7:20:15 AM. Contact: ###-####. doors with mag hold opens require smoke detectors for door release; penetrations in three hour wall require firestopping; exit sign needed as shown on plans; door to east stair to have passage set; fire sprinklers within 6 ft of each other by west exit; smoke detector required above FACP 1/16/2004 3:01:51 PM
FIR03-00698 INSP-Final Inspection1/16/20041/16/20041/16/2004 12:00:00 AMAFAIL
duct detector not shutting AHU off; had to adjust strobes to proper CD in several areas; need updated map and record of completion 1/16/2004 11:05:19 AM
FIR03-00759 INSP-Sprinkler Rough-in1/16/20041/16/20041/16/2004 12:00:00 AMPFAIL
installed per plans however there are two heads located within 6 ft of each other - located by west exit doors 1/16/2004 2:39:57 PM
FIR03-00302 INSP-Final Inspection1/16/20041/16/20041/16/2004 12:00:00 AMPPASS