Inspections for the day of: Friday, January 16, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS04-00009 FIR-Final1/15/20041/16/20041/16/2004 12:00:00 AMAPART
A temporary occupancy was given. The tenant needs to re-install the canopy on one sprinkler pendant that has fallen off. Also one of the duct smoke detectors in this tenant space is in alarm/supervisory. The remote LED is lit up. The fire alarm panel is in trouble. This will need to be fixed prior to receiving a permanant occupancy. Correction notice was left with tenant representative. 1/16/2004 10:22:28 AM
FIR03-00747 INSP-Final Inspection1/14/20041/16/20041/16/2004 12:00:00 AMAPASS
Hood suppression system operated correctly 1/16/2004 8:55:21 AM
FIR03-00748 INSP-Final Inspection1/14/20041/16/20041/16/2004 12:00:00 AMAPASS
Hood suppression system operated correctly 1/16/2004 8:55:27 AM
FIR03-00258 INSP-Alarm Testing1/15/20041/16/20041/16/2004 12:00:00 AMPFAIL
Demo old fire alarm system, 185cd a/v's in room A38 are oerspaced. They exceed 35' from the walls. Provide strobe coverage in A38 mezzanine. Provide strobe in corridor behind A37. Provide strobe in unmarked toilet north of A27. Provide strobe in toilet A28. Resubmit plans per review note #2. 1/16/2004 3:06:49 PM
FIR03-00539 INSP-Final Inspection1/13/20041/16/20041/16/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 1/13/2004 at 1:59:45 PM. Contact: ###-####.
BLD03-02840 FIRE-Final Inspection1/15/20041/16/20041/16/2004 12:00:00 AMPPASS
fire life safety OK 1/16/2004 2:11:35 PM
BLD03-02842 FIRE-Final Inspection1/15/20041/16/20041/16/2004 12:00:00 AMPPASS
fire life safety OK 1/16/2004 2:12:05 PM
FIR03-00501 INSP-Conference1/15/20041/16/20041/16/2004 12:00:00 AMPDONE
Discussed head spacing around the file cabinets 1/16/2004 3:04:06 PM
FIR03-00760 INSP-Sprinkler Rough-in1/16/20041/16/20041/16/2004 12:00:00 AMPFAIL
see approved sprinkler plans for locations where the insulation for the tenting of the sprinkler piping is not secured 1/16/2004 3:01:02 PM
BLD01-03108 FIRE-Final Inspection1/16/20041/16/20041/16/2004 12:00:00 AMPPASS
BLD01-03111 FIRE-Final Inspection1/16/20041/16/20041/16/2004 12:00:00 AMPPASS