BLD06-02377
| FIRE-Final Inspection | 1/15/2007 | 1/16/2007 | 1/17/2007 8:51:02 AM | A | PASS |
|
|
Corrections have been verified, fire life safety inspection passed.
|
FIR06-00963
| INSP-Final Inspection | 1/15/2007 | 1/16/2007 | 1/17/2007 8:50:24 AM | A | PASS |
|
|
Field corrections are complete, fire alarm permit finaled.
|
BLD06-02377
| FIRE-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 4:12:22 PM | P | DONE |
|
|
Duplicate inspection request.
|
BLD06-00688
| FIRE-Conference | 1/9/2007 | 1/16/2007 | 1/16/2007 3:53:23 PM | P | DEFR |
|
|
To be completed on 1/17 as agreed per telecon.
|
FIR06-00596
| INSP-Final Inspection | 1/10/2007 | 1/16/2007 | 1/16/2007 3:43:56 PM | P | CANC |
|
|
No time to complete inspection due to high volume of scheduled requests.
|
FIR06-00715
| INSP-Final Inspection | 1/15/2007 | 1/16/2007 | 1/16/2007 3:42:51 PM | P | CANC |
|
|
No time to complete inspection due to high volume of scheduled requests.
|
FIR06-00755
| INSP-Sprinkler Rough-in | 1/16/2007 | 1/16/2007 | 1/16/2007 3:39:18 PM | P | FAIL |
|
|
UG fire supply line is NOT approved for cover as the trenches are backfilled to the point that a sufficient inspeciton cannot be performed due to piping concealment. Contractor needs to expose the installation for viewing and request an additional inspection.
|
BLD04-02464
| FIRE-Supply Line Flush | 1/16/2007 | 1/16/2007 | 1/16/2007 3:24:14 PM | P | NR |
|
|
Lacking coordination to provide water supply for UG fire line flush.
|
FIR06-00764
| INSP-Final Inspection | 1/11/2007 | 1/16/2007 | 1/16/2007 2:51:24 PM | A | PART |
|
|
Sprinkler install appears satisfactory with respect to heads and spacing, however no access was provided above ceiling to verify pipe size, routing, attatchment methods, etc., final pending inspection of these items at next visit.
|
BLD06-00236
| FIRE-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 1:42:25 PM | A | PASS |
|
|
Required corrections have been finished, fire life safety finaled.
|
FIR06-00677
| INSP-Final Inspection | 1/12/2007 | 1/16/2007 | 1/16/2007 1:41:18 PM | A | PASS |
|
|
Final fire sprinkler inspection passed, permit finaled.
|
FIR05-00772
| INSP-Sprinkler Rough-in/Hydro | 1/15/2007 | 1/16/2007 | 1/16/2007 1:22:26 PM | A | FAIL |
|
|
Air test failed due to start pressures below the min. amount allowed per NFPA 13.
|
MIS06-00285
| FIR-Final | 1/12/2007 | 1/16/2007 | 1/16/2007 12:57:51 PM | A | PASS |
|
|
One emergency light/exit sign at the main entry repaired while on site. Life safety inspection is acceptable.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 1/12/2007 | 1/16/2007 | 1/16/2007 12:22:38 PM | A | PART |
|
|
Inspection for the OH rough-in at the 4th floor SE quad portion as marked on approved plans is okay for cover, noted one head in a conference room to be relocated due to overspacing, one beam clamp in the men's restroom needs adjustment, walls for one room have not been built as shown on plans which may affect coverage if constructed as indicated, sprinklers in the electrical and telephone rooms shall be temp. rated per NFPA 13 2002 8.3.2.1, noted max. bending raduis must not be exceeded for flex head piping per manufacturer requirements, hydrostatic test for this portion of work is acceptable per discussion.
|
BLD06-02301
| FIRE-Final Inspection | 1/12/2007 | 1/16/2007 | 1/16/2007 11:18:07 AM | A | PASS |
|
|
Fire life safety inspection passed, noted one existing exit sign not functional on battery backup to be repaired today per agreement with contractor, also noted missing handle at the fire extinguisher cabinet to be installed ASAP.
|
BLD06-02052
| FIRE-Final Inspection | 1/15/2007 | 1/16/2007 | 1/16/2007 10:56:12 AM | A | PASS |
|
|
Fire life safety inspection is satisfactory.
|
FIR06-00646
| INSP-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 10:55:15 AM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR06-00504
| INSP-Conference | 1/11/2007 | 1/16/2007 | 1/16/2007 10:36:19 AM | A | DONE |
|
|
On site conference to discuss fire related HVAC issues.
|