FIR06-00984
| INSP-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 5:40:02 PM | P | PASS |
|
|
permit finaled
|
BLD05-03023
| FIRE-Final Inspection | 1/15/2007 | 1/16/2007 | 1/16/2007 5:39:03 PM | P | PASS |
|
|
Life safety passed.
|
FIR06-00222
| INSP-Final Inspection | 1/11/2007 | 1/16/2007 | 1/16/2007 3:07:29 PM | P | CANC |
|
|
Per contractor the project is not ready for a final inspection
|
BLD06-00907
| FIRE-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 2:43:53 PM | P | PASS |
|
|
Life safety finaled
|
FIR06-00789
| INSP-Sprinkler Rough-in/Hydro | 1/11/2007 | 1/16/2007 | 1/16/2007 12:52:00 PM | A | PASS |
|
|
Overhead hydro test passed.
|
BLD06-02662
| FIRE-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 12:35:55 PM | P | PASS |
|
|
permit finaled
|
BLD06-02501
| FIRE-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 12:35:34 PM | P | PASS |
|
|
life safety finaled
|
FIR07-00021
| INSP-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 11:12:53 AM | P | PASS |
|
|
permit finaled
|
FIR07-00021
| INSP-Final Inspection | 1/12/2007 | 1/16/2007 | 1/16/2007 11:10:05 AM | A | PASS |
|
|
permit finaled
|
BLD06-01467
| FIRE-Final Inspection | 1/12/2007 | 1/16/2007 | 1/16/2007 11:03:45 AM | A | PASS |
|
|
Life safety finaled
|
BLD06-01466
| FIRE-Final Inspection | 1/12/2007 | 1/16/2007 | 1/16/2007 11:01:11 AM | A | PASS |
|
|
life safety finaled
|
FIR06-00829
| INSP-Final Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 11:00:39 AM | P | PASS |
|
|
permit finaled
|
FIR06-00977
| INSP-Sprinkler Rough-in/Hydro | 1/15/2007 | 1/16/2007 | 1/16/2007 10:57:41 AM | A | PASS |
|
|
The remaining areas of the 2nd floor tenant inprovement are ok to cover.
|
FIR06-00774
| INSP-Sprinkler Rough-in/Hydro | 1/12/2007 | 1/16/2007 | 1/16/2007 9:48:52 AM | A | FAIL |
|
|
Need to redo the test since the account had not been set up at the monitoring agency. Also need the map at the facp.
|
FIR06-00631
| INSP-Final Inspection | 1/15/2007 | 1/16/2007 | 1/16/2007 9:46:37 AM | A | FAIL |
|
|
Provide correct backflow or data sheet proving friction loss as calculated has not been exceeded. Provide forward flush. Provide permanant heat, insulation above ceiling in the riser room and provide a one hour rated room.
|
FIR06-00803
| FIR-Aging Inspection | 1/16/2007 | 1/16/2007 | 1/16/2007 9:02:00 AM | | NR |
|
|
work is still in progress
|
MIS06-00338
| FIR-Final | 1/16/2007 | 1/16/2007 | 1/16/2007 12:00:00 AM | P | CANC |
|
|
Need earlier inspection before customers come in
|